49
5.3.4.3
Reading parameters
Register
hex. no.
Register
decimal
no.
Description
Format
Type
Values displayed
Dampers accessible in read-only mode (functions 3 or 4)
0x44C
1100
Supply air temperature
Integer
Read-only
Value x10
0x44D
1101
Return air temperature
Integer
Read-only
Value x10
0x44E
1102
Ambient temperature
Integer
Read-only
Value x10
0x44F
1103
Fresh air temperature
Integer
Read-only
Value x10
0x450
1104
Water network temperature
Integer
Read-only
Value x10
0x453
1107
Filter CF2 pressure switch control input state
Boolean
Read-only
0 = No fault
1 = Fault
0x454
1108
Supply air fan flow rate
Integer
Read-only
Value /10
0x455
1109
Return air fan flow rate
Integer
Read-only
Value /10
0x456
1110
Duct pressure
Integer
Read-only
0x458
1112
Supply air filter CF1 fouling
Integer
Read-only
0x459
1113
Return air filter CF1 fouling
Integer
Read-only
0x45C
1116
Air quality in ppm of CO
2
Integer
Read-only
0x45E
1118
Supply air fan monitoring input state
Boolean
Read-only
0 = Contact open
1 = Contact closed
0x45F
1119
Return air fan monitoring input state
Boolean
Read-only
0 = Contact open
1 = Contact closed
0x460
1120
Fire input state
Boolean
Read-only
0 = Fault
1 = No fault
0x467
1127
Humidifier monitoring
Boolean
Read-only
0 = Fault
1 = No fault
0x468
1128
Electric heater load shedding command or Selection of
heating coil
Boolean
Read-only
0 = Not Shed / EC
1 = Load shedding / EL
0x469
1129
Remote control input state
Boolean
Read-only
0 = Off
1 = On
0x46C
1132
Electric heater safety thermostat input state
Boolean
Read-only
0 = Fault
1 = No fault
0x46E
1134
Antifreeze thermostat input state
Boolean
Read-only
0 = No fault
1 = Fault
0x474
1140
Supply air variable drive command signal
Integer
Read-only
0x475
1141
Return air variable drive command signal
Integer
Read-only
0x476
1142
Opening percentage for coil 1
Integer
Read-only
0x477
1143
Opening percentage for coil 2
Integer
Read-only
0x47D
1149
"Danger" fault summary relay
Boolean
Read-only
0 = No fault
1 = Fault
0x47E
1150
"Maintenance" fault summary relay
Boolean
Read-only
0 = No fault
1 = Fault
0x483
1155
Damper servomotor state
Boolean
Read-only
0 = Damper closed
1 = Damper open
0x484
1156
Stage 1 state for the electric heater
Boolean
Read-only
0 = Off
1 = On
0x485
1157
Stage 2 state for the electric heater
Boolean
Read-only
0 = Off
1 = On
0x488
1160
Stage state for the DX coil
Boolean
Read-only
0 = Off
1 = On
0x48E
1166
Humidifier operation authorisation output state
Boolean
Read-only
0 = Off
1 = On
0x491
1169
Mixing output value
Integer
Read-only
0x492
1170
Mixing command direction of action
Integer
Read-only
0:Non
1:Opening
2:Closed