20
1.7
Controller inputs and outputs
G
24Vac
G0
Shared
1.7.1
Analogue inputs
Connector J3
B1
Return air temperature sensor (Option)
B2
Supply air temperature sensor
B3
Fresh air temperature sensor (Option)
B4
Network water temperature sensor (Option)
B5
Supply air filter CF1 fouling level pressure sensor
B6
Supply air fan flow rate pressure sensor (Option)
B7
Return air fan flow rate pressure sensor (Option)
GND
Shared
Connector J18
B8
----------
B9
----------
B10
Return air filter CF1 fouling level pressure sensor
B11
Air quality sensor (Option)
B12
Supply air duct pressure sensor (Option)
1.7.2
Digital inputs
Connector J4
DI1
Supply air fan monitoring
DI2
Return air fan monitoring
DI3
Filter CF2 pressure switch (optional)
DI4
Frost protection thermostat (Option)
DI5
Remote control
DI6
Load shedding (Option)
DI7
Monitoring of electric heater overheating thermostat (Option)
DIC1
Shared
Connector J16
DI8
Fire (Option)
DI9
Humidifier fault summary (Option)
DI10
Heat recovery unit fouling level pressure switch (Option)
DIC2
Shared
1.7.3
Analogue outputs
Connector J5
Y1
Supply air fan speed 0-10V control
Y2
Return air fan speed 0-10V control (Option)
Y3
0-10V control for the coil 1 water valve (Option)
Y4
0-10V control for the coil 2 water valve (Option)
GND
Shared
1.7.4
Digital outputs
Connector J12
NO1
----------
NO2
----------
NO3
Condensation unit On control
C1
Shared
Connector J13
NO4
Stage 1 control for the electric heaters
NO5
Stage 2 control for the electric heaters
NO6
Danger alarms summary relay
C2
Shared