23
2.1.1
Access level selection menu
There are now three access levels:
-
Level 1: User
-
Level 2: Installer
-
Level 3: Manufacturer
2.2
Setpoint menu
Comfort w0
Indication of the operating mode.
Level 2 access
Fan flow rate
Supply air 02000m3/h Supply air fan Comfort flow rate control setpoint
Return air 02000m3/h
Return air fan Comfort flow rate control setpoint
Eco
Supply air 01000m3/h Supply air fan Eco flow control setpoint
Return air 01000m3/h
Return air fan Eco flow control setpoint
Comfort w1
Indication of the operating mode.
Level 2 access
Duct pressure
200Pa
Comfort pressure control setpoint for the Supply air duct
Eco 100Pa
Eco pressure control setpoint for the Supply air duct
Comfort w2
Indication of the operating mode for T° regulation in "Precision" mode
Level 1 access
Return air 20.0°c
Comfort (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Eco 15.0°c
Eco (Return or Ambient air) temperature control setpoint monitored (0 to 50.0°C)
Supply air
Upper limit 26.0°c
Upper limit for calculated Supply air T° setpoint
Lower limit 16.0°c
Lower limit for calculated Supply air T° setpoint
w3
Level 2 access
Air quality
0800ppm CO2
Air quality control setpoint
Maximum flow rate
03000m3/h
Maximum flow rate value of supply air fan for air quality control
Comfort w4
Indication of the operating mode for T° regulation in "Energy optimisation" mode
Level 1 access
Return air Cooling 25.0°c Comfort Cooling (Return, Ambient or Supply air) temperature control setpoint monitored (0 to 50.0°C)
Eco 27.0°c
Eco Cooling (Return, Ambient or Supply air) temperature control setpoint monitored (0 to 50.0°C)
Return air Heating 23.0°c
Comfort Cooling (Return, Ambient or Supply air) temperature control setpoint monitored (0 to 50.0°C)
Eco 18.0°c
Eco Cooling (Return, Ambient or Supply air) temperature control setpoint monitored (0 to 50.0°C)
Deadband
Indication of the control state for the monitored temperature