Remote Operation
5-31
20. CONFigure:INTERLOCK:PULL
Description: It controls the internal resistance status of Safety Interlock input
signal.
Syntax:
CONFigure:INTERLOCK:PULL <ARG>
Parameter: LOW|HIGH
Example:
CONFigure:INTERLOCK:PULL LOW
CONFigure:INTERLOCK:PULL HIGH
Query Syntax:
CONFigure:INTERLOCK:PULL?
Return Parameter: LOW | HIGH
Query Example:
CONF:INTERLOCK:PULL?
Return Example:
LOW
21. CONFigure:EXTON
Description: It enables the External ON/OFF control.
Syntax:
CONFigure: EXTON <ARG>
Parameter: DISABLE| ENABLE
Example:
CONFigure: EXTON DISABLE
CONFigure: EXTON ENABLE
Query Syntax:
CONFigure: EXTON?
Return Parameter: DISABLE | ENABLE
Query Example:
CONF: EXTON?
Return Example:
DISABLE
22. CONFigure: EXTON:PULL
Description: It controls the internal resistance status of External ON/OFF input
signal.
Syntax:
CONFigure: EXTON:PULL <ARG>
Parameter: LOW|HIGH
Example:
CONFigure: EXTON:PULL LOW
CONFigure: EXTON:PULL HIGH
Query Syntax:
CONFigure: EXTON:PULL?
Return Parameter: LOW | HIGH
Query Example:
CONF: EXTON:PULL?
Return Example:
LOW