6. OPERATION/SETTING
6.8 Alarm Setting
All DIP Switches: OFF
[Dot-printing type]
Is channel the one you desire to
set indicated by the dotter?
YES
Move the pointer to the scale you desire for the
alarm to be activated by pressing
◄
/
►
keys.
The pointer moves to the current alarm value
or initial position.
YES
NO
Recording mode
Place AUTO CH switch in the down position.
(One-point indication mode)
Press MODE switch.
Alarm level select lamp “L” lights.
Alarm level select lamp “H” lights.
“
L” level: Transition to lower limit
alarm setting mode
“
H” level: Transition to upper limit
alarm setting mode
Do you want to set the “H”
level alarm, too?
The pointer moves to the current alarm value
or initial position.
Move the pointer to the scale you desire for the
alarm to be activated by pressing
◄
/
►
keys.
Do you want to set the “L”
level alarm, too?
NO
YES
* When the instrument has a
single scale, you do not need to
check the channel indicated by
the dotter.
Points where operations
of the instrument are
needed
Points where the instrument
operates
Select the alarm level with
◄
/
►
keys.
NO
Alarm lamp blinks and the alarm setting value is written.
Alarm lamp blinks and the alarm setting value is written.
Place AUTO CH switch in the up position.
Recording mode
Flow Chart of Alarm Setting
Press MODE switch.
ALARM lamp blinks.
Press ENTRY key.
ALARM lamp lights.
Alarm level select lamp “L” blinks.
Press ENTRY key.
Press ENTRY key.
Press ENTRY key.
RUN lamp and chart speed indication lamp light.