- 57 -
[List of Calc setting parameters]
Parameter
Function
Default
Set value
Kind
Select calculation type
None
None (No calculation), Root (square root),
LOGe (natural logarithm), LOG10 (common logarithm),
INT (integration),
Humidity (humidity/temperature calculation)
COM.Input (data communications input),
MUL (arithmetic 1), DIV (arithmetic 2),
High-Peak (max value), Low-Peak (min value),
Average (average calculation), Power (exponent),
ABS (absolute value calculation)
Formula, BrokenLine (broken line approximation)
Decimal point
Set decimal point position for result
*
0 to 3
Form.No.
Specify formula No. when “Formula”
is selected for Kind
*
- (None), 1 to 12
Seg.Table No.
Specify broken line table No. when
“BrokenLine” is selected for Kind
*
- (None), 1 to 6
CH.X
Specify CH for X data used by each
calculation
*
- (None), 1 to 4
CH.Y
Specify CH for Y data used by each
calculation
*
- (None), 1 to 4
Const.A
Set calculation constant A when
arithmetic 1 or 2 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.B
Set calculation constant B when
arithmetic 1 or 2 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.C
Set calculation constant C when
arithmetic 1 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
Const.D
Set calculation constant D when
arithmetic 1 is selected for Kind
*
-30000 to 99999
Up to three digits after decimal point can be set.
Example: -30.000
[Start]
Set calculation start time
Calculation is waited until set time
(data during the waiting period is
invalid).
*
- (None), 00 : 00 to 23 : 59
When “-“ is set, following operations are performed.
Integration: Operated by external reset
Formula: Operated at power-on or immediately after
setting is made
[Interval]
Set calculation interval
For calculations using integration,
integration value is reset at set
intervals.
*
- (None), 00 : 00 to 24 : 59
Setting “-“ or “00 : 00” disables interval.
TimeUnit
Unit of integration time
*
Hour, Min, Sec
INT-Reset
Set integration reset method for
calculations using integration
*
None (reset not performed), Interval (specified interval),
EX (All) (all reset by remote contact), EX (individual reset
by remote contact)
INT-Reset.EX
Specify remote contact No. used
when “EX” is selected for "INT-Reset"
*
- (None), 1 to 10