- 123 -
3. Transmission condition setting
Set the E-mail transmission condition. E-mail can be sent at alarm activation (when alarm is activated on the specified
channel), at set time (at every interval from reference time) or at occurrence of event like chart end (see “8-22. Fail
Output Settings”). Up to six conditions can be registered.
(1) Pressing
the
key displays the
menu window (list of setting items).
(2) Select
“E-mail”.
(3) Move the cursor to Setting beside
“Condition” and press the
key.
(4) Move the cursor to the target condition No.
with the
▲
/
▼
keys and press the
key. The cursor does not move to
parameters other than No.
(5) Move the cursor to the parameter to be set
with the
▲
/
▼
/
/
keys.
(6) Press
the
key to make it available
for setting and then select or enter a value.
(7) After completing the settings of this item,
move the cursor to Set .
(8) Press
the
key to register the
settings (when chart recording is ON, a
setting change mark is printed). To cancel
the settings, press the
key.
[List of E-mail Condition setting parameters]
Parameter
Function
Default
Set value
Condition
Select E-mail transmission condition
None
None (not used), Alarm (at alarm activation),
Interval (send measured value at fixed intervals),
FailOut
[Target CH]
Set beginning and end of target CHs to send
e-mail for alarm activation or measured value
*
1 to 4
[Std.TIME]
Set reference time for sending measured data
*
00:00 to 23:59
[Interval]
Set interval for sending measured data
*
00:00 to 24:59
[Address No.]
Select destination address for each condition
Select up to three addresses from those set in the
previous section by checking desired address No.
Note: Actual windows are separated. Use the
▲
/
▼
keys to
scroll and continue settings
E-mail is sent at the following time: reference time + (interval x n)
n = 0, 1, 2, 3…
Example: [Std.TIME] is set to “00:00” and [Interval] is set to “04:00”
E-mail will be sent at 00:00, 04:00, 08:00, 12:00, 16:00 and 20:00.
Interval setting
Reference