- 93 -
[List of FailOut setting parameters]
Parameter
Function
Default
Set value
Chart End
Set alarm operation at detection of
chart end
Not selected
LCD (LCD display), LED (LED indication),
E-mail, Relay (relay output)
Check a check box of desired item.
Chart End Relay No.
Set alarm output relay No. at
detection of chart end
-
- (No output), 99 (internal circuit output), 1 to
12
Chart End And/Or
Select circuit type of alarm output
at detection of chart end
Or And,
Or
Burn
Set alarm operation at detection of
input disconnection
Not selected
LCD (LCD display), LED (LED indication),
E-mail, Relay (relay output)
Check a check box of desired item.
Burn Relay No.
Set alarm output relay No. at
detection of input disconnection
-
- (No output), 99 (internal circuit output), 1 to
12
Burn And/Or
Select circuit type of alarm output
at detection of input disconnection
Or And,
Or
SD Card
Set alarm operation at detection of
SD card low capacity
Not selected
LCD (LCD display), LED (LED indication),
E-mail, Relay (relay output)
Check a check box of desired item.
SD Card Relay No.
Set alarm output relay No. at
detection of SD card low capacity
-
- (No output), 99 (internal circuit output), 1 to
12
SD Card And/Or
Select circuit type of alarm output
at detection of SD card low
capacity
Or And,
Or
Battery
Set alarm operation at detection of
backup battery low level
Not selected
LCD (LCD display), LED (LED indication),
E-mail, Relay (relay output)
Check a check box of desired item.
Battery Relay No.
Set alarm output relay No. at
detection of backup battery low
level
-
- (No output), 99 (internal circuit output), 1 to
12
Battery And/Or
Select circuit type of alarm output
at detection of backup battery low
level
Or And,
Or
System Error
Set alarm operation at detection of
system error
Not selected
LCD (LCD display), LED (LED indication),
E-mail, Relay (relay output)
Check a check box of desired item.
System Error Relay
No.
Set alarm output relay No. at
detection of system error
-
- (No output), 99 (internal circuit output), 1 to
12
System Error And/Or
Select circuit type of alarm output
at detection of system error
Or And,
Or