- 71 -
8-10. Periodic (Data Interval) Data Printing Settings “DataInt”
In addition to the trace printing on a chart, measured data of each channel can be printed numerically. Measured data can
be recorded or printed digitally at desired intervals. Select ON/OFF to enable or disable digital recording/printing for each
channel (DIGI.REC) in input type settings described in “8-2. Input Type Settings”.
(1) Pressing
the
key displays the
menu window (list of setting items).
(2) Select
“DataInt”.
(3) Move the cursor to the parameter to be set
with the
▲
/
▼
/ /
keys.
(4) Press
the
key to make it available
for setting and then enter a value.
(5) After completing the setting of this item,
move the cursor to Set .
(6) Press
the
key to register the
settings (when chart recording is ON, a
setting change mark is printed). To cancel
the settings, press the
key.
[List of DataInt setting parameters]
Parameter
Function
Default
Set value
StartTime
Set start time of periodic data printing
(When a set time is before the current
time, periodic data printing is executed
next day.)
00 : 00
00 : 00 to 23 : 59
Interval
Set interval between printings of numeric
measured data (every 24 hours 59
minutes and 1 minute at maximum)
00 : 00
00: 00 to 24 : 59
The shortest interval depends on the chart speed and the number of digital recording/printing channels. If a set
interval is inappropriate for the specified chart speed, printing will be executed with a timing of the minimum integral
multiple of the interval.
Interval [M]
≥
Note: Interval less than 5min cannot be set.
*1: The lowest speed of three speeds is used.
*2: Differs depending on the chart speed and the number of digital recording/printing channels.
Chart speed
1CH
2CH
3CH
4CH
99mm
/
H or less
1 row
2 row
100mm
/
H or more
1 row
2 row
3 row
4 row
Note: This differs from the number of skipped channels.
Calculating the shortest interval
Reference
180 x printing lines *2
Chart speed [mm/H] *1