- 115 -
2) Operations allocated to arbitrary terminal numbers
ON: short OFF: open
Operation name
Terminal contact signal
(4) Data
printing
Turn ON the terminal No. specified for data printing.
Chart recording should be ON.
Data printing can be executed also by keys.
While executing data printing, another execution request can be accepted.
(5) List
printing
(List No.1, 2 and 3)
Turn ON the terminal No. specified for list 1, 2 and 3 printing.
Chart recording should be ON.
List printing can be executed also by keys.
(See “8-12. List Printing Settings”.)
(6) Integration value reset
When “EX (All)” is selected for INT-Reset in calculation settings, integration value can be
reset by turning ON the terminal No. specified for integration reset.
(See “8-4. Calculation Settings”.)
(7) Message
printing
(No.01 to No.20)
Message should be set as well as the setting described in this section.
(See “8-13. Message Printing 1 Settings”.)
Turn ON the terminal No. specified for message printing (No.01 to 20).
Chart recording should be ON.
Message printing can be executed also by keys.
(8) Time
correction
When the current time (second) is 0 to 30, the second value will be set to 0. When it is 31
to 59, the minute value will be increased by 1min and the second value will be set to 0.
Example: Turn On the specified terminal No. at 10:10 and 30 seconds.
The time will be set to 10:10:00.
It will be 10:11:00 when the terminal is turned ON at 10:10 and 31 seconds.
For contact signal which is given to remote contact terminal, use a switch or relay
operated at 30V AC, 60V DC or lower voltage level, or manually operated contact
which can handle minute load.
1sec or more
!
Warning