60Hz IEC compressors with Siemens motors
Compressor
type
Supply
voltage (V)
Overload relay
(A)
Fuses Class gL/
gG (Type 2) (A)
2X3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 1) (A)
3 fuses
2X3 cables to
contactor
Fuses Class gL/
gG (Type 1) (A)
3 fuses
3 cables to
contactor
(bridges to be
installed by
customer)
200 kW (270
hp)
380
233
2x (3x355)
--
--
200 kW (270
hp)
440-460
218
2x (3x300)
--
--
250 kW (340
hp)
380
291
2x (3x400)
--
--
250 kW (340
hp)
440-460
256
2x (3x315)
--
--
60 Hz CSA/UL compressors with WEG motor
Compressor
type
Supply
voltage (V)
Overload relay
(A)
Fuses CSA HRC
UL Class 5 (A)
2x3 fuses
2x3 cables to
contactor
Fuses UL Class
K5 (A)
3 fuses
2x3 cables to
contactor
Fuses UL Class
K5 (A)
3 fuses
3 cables to
contactor
(bridges to be
installed by
customer)
200 kW (270
hp)
440-460
215
2x (3x300)
3x450
--
200 kW (270
hp)
575
165
2x (3x250)
3x350
--
250 kW (340
hp)
440-460
245
2x (3x300)
3x500
--
250 kW (340
hp)
575
187
2x (3x250)
3x400
--
9.6
Settings of circuit breakers
For cooler cooling fan (air-cooled 50 Hz)
Compressor type
Supply voltage (V)
Circuit breakers
Setting (A)
200 kW (270 hp)
230
Q25/Q26
17.1
200 kW (270 hp)
400
Q25/Q26
9.9
200 kW (270 hp)
500
Q25/Q26
7.7
250 kW (340 hp)
230
Q25/Q26
17.1
250 kW (340 hp)
400
Q25/Q26
9.9
Instruction book
2920 1796 01
107
Summary of Contents for CPF 270
Page 1: ...CPF 270 CPF 340 Instruction book ...
Page 2: ......
Page 61: ...Instruction book 2920 1796 01 59 ...
Page 93: ...Vent filler and drain plugs on air cooled compressors Instruction book 2920 1796 01 91 ...
Page 120: ......
Page 121: ......
Page 122: ...No 2920 1796 01 2013 02 ...