![CG Emotron VFX Series Instruction Manual Download Page 223](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388223.webp)
CG Drives & Automation, 01-5326-01r5
Troubleshooting, Diagnoses and Maintenance
221
Comm error
Error on serial communication (option)
-
Check cables and connection of the
serial communication.
-
Check all settings with regard to the
serial communication
-
Restart the equipment including the
AC drive
Crane Deviat
CRANE board detecting deviation in motor
operation.
NOTE: Only used in Crane Control.
-
Check encoder signals
-
Check Deviation jumper on Crane option board.
-
Check the settings in menus [3AB] & [3AC]
CraneComm
Lost communication with CRANE board.
NOTE: Only used in Crane Control.
-
Check CRIO board
-
Check CRIO cable and signals.
Encoder
Lost encoder board, encoder cable or
encoder pulses.
Motor speed deviation in between reference
and measured speed detected.
NOTE: Only valid if option board Encoder is
used.
-
Check encoder board.
-
Check encoder cable and signals.
-
Check motor operation.
-
Check speed deviation settings [22G#].
-
Check speed PI controller settings [37#].
-
Check torque limit setting [351]
-
Disable encoder, set menu [22B] to OFF.
Pump
No master pump can be selected due to
error in feedback signalling.
NOTE: Only used in Pump Control.
-
Check cables and wiring for Pump feedback
signals
-
Check settings with regard to the pump feedback
digital inputs
Over temp
Heatsink temperature too high:
-
Too high ambient temperature of the
AC drive
-
Insufficient cooling
-
Too high current
-
Blocked or stuffed fans
-
Check the cooling of the AC drive cabinet.
-
Check the functionality of the built-in fans.
The
fans must switch on automatically if the heatsink
temperature gets too high. At power up the fans
are
briefly switched on.
-
Check AC drive and motor rating
-
Clean fans
Over curr F
Motor current exceeds the peak AC drive
current:
-
Too short acceleration time.
-
Too high motor load
-
Excessive load change
-
Soft short-circuit between phases or
phase to earth
-
Poor or loose motor cable connections
-
Too high IxR Compensation level
-
Check the acceleration time settings and
make them longer if necessary.
-
Check the motor load.
-
Check on bad motor cable connections
-
Check on bad earth cable connection
-
Check on water or moisture in the motor housing
and cable connections.
-
Lower the level of IxR Compensation [352]
Over volt
D(eceleration)
Too high DC Link voltage:
-
Too short deceleration time with
respect
to
motor/machine inertia.
-
Too small brake resistor malfunctioning
Brake chopper
-
Check the deceleration time settings and make
them longer if necessary.
-
Check the dimensions of the brake resistor and
the functionality
of the Brake chopper (if used)
Over volt
G(eneration)
Over volt (Mains)
Too high DC Link voltage, due to too high
mains voltage
-
Check the main supply voltage
-
Try to take away the interference cause or
use
other main supply lines.
O(ver) volt
M(ains) cut
Over speed
Motor speed measurement exceeds
maximum level. 110% of max speed (all
parameter sets).
-
Check encoder cables, wiring and setup
-
Check motor data setup [22x]
-
Perform short ID-run
Under voltage
Too low DC Link voltage:
-
Too low or no supply voltage
-
Mains voltage dip due to starting other
major power consuming machines on
the same line.
-
Make sure all three phases are properly connected
and that the terminal screws are tightened.
-
Check that the mains supply voltage is within the
limits of the AC drive.
-
Try to use other mains supply lines if dip is caused
by other machinery
-
Use the function low voltage override [421]
Table 44
Trip condition, their possible causes and remedial action
Trip condition
Possible Cause
Remedy
Size**
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......