![CG Emotron VFX Series Instruction Manual Download Page 153](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388153.webp)
CG Drives & Automation,01-5326-01r5
Functional Description
149
If the speed of the master drive comes into the upper band,
an additional drive will be added after a delay time that is set
in “Start delay [399]”.
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Upper Band = 10%
Start delay will be activated:
Range = Max Speed to Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 1500–120 = 1380 rpm
Fig. 115 Upper band
Lower Band [398]
If the speed of the master drive comes into the lower band
an additional drive will be stopped after a delay time. This
delay time is set in the parameter “Stop Delay [39A]”.
Communication information
Example:
Max Speed = 1500 rpm
Min Speed = 300 rpm
Lower Band = 10%
Stop delay will be activated:
Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 300 + 120 = 420 rpm
Fig. 116 Lower band
397
Upper Band
Default:
10%
Range:
0-100% of total min speed to max speed
Modbus Instance no/DeviceNet no:
43167
Profibus slot/index
169/71
EtherCAT and CANopen index (hex)
4c5f
Profinet IO index
19551
Fieldbus format
Long, 1=1%
Modbus format
EInt
398
Lower Band
Default:
10%
Range:
0-100% of total min speed to max speed
(NG_50-PC-12_1)
Flow/Pressure
Speed
Max
Min
Upper band
next pump starts
Start Delay [399]
Modbus Instance no/DeviceNet no:
43168
Profibus slot/index
169/72
EtherCAT and CANopen index (hex)
4c60
Profinet IO index
19552
Fieldbus format
Long, 1=1%
Modbus format
EInt
(NG_50-PC-13_1)
Speed
Max
Min
“top” pump stops
Lower band
Stop Delay [39A]
Flow/Pressure
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......