CG Drives & Automation,01-5326-01r5
169
AnIn1 Function Min [5134]
With AnIn1 Function Min the physical minimum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511].
Table 36 shows corresponding values for the min and max
selections depending on the function of the analogue input
[511].
Communication information
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5134].
Communication information
AnIn1 Function Max [5136]
With AnIn1 Function Max the physical maximum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511]. See
Table 36.
Communication information
AnIn1 Function Value Max [5137]
With AnIn1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5136].
Communication information
Example:
Process sensor is a sensor with the following specification:
Range:
0–3 bar
Output:
2–10 mA
Analogue input should be set up according to:
[512] AnIn1 Setup = User mA
[5131] AnIn1 Min = 2 mA
[5132] AnIn1 Max = 10 mA
[5134] AnIn1 Function Min = User-defined
[5135] AnIn1 VaMin = 0.000 bar
[5136] AnIn 1 Function Max = User-defined
[5137] AnIn1 VaMax = 3.000 bar
5134
AnIn1 FcMin
Default:
Min
Min
0
Min value
Max
1
Max value
User-
defined
2
Define user value in menu [5135]
Table 36
AnIn Function
Min
Max
Speed
Min Speed [341]
Max Speed [343]
Torque
0%
Max Torque [351]
Process Ref
Process Min [324]
Process Max [325]
Process Value
Process Min [324]
Process Max [325]
Modbus Instance no/DeviceNet no:
43206
Profibus slot/index
169/110
EtherCAT and CANopen index (hex)
4c86
Profinet IO index
19590
Fieldbus format
UInt
Modbus format
UInt
5135
AnIn1 VaMin
Default:
0.000
Range:
-10000.000 – 10000.000
Modbus Instance no/DeviceNet no:
43541
Profibus slot/index
170/190
EtherCAT and CANopen index (hex)
4dd5
Profinet IO index
19925
Fieldbus format
Long, 1=1 rpm, 1 %, 1°
or 0.001 if Process Value/
Process Ref using a [322]
unit
Modbus format
EInt
5136
AnIn1 FcMax
Default:
Max
Min
0
Min value
Max
1
Max value
User-
defined
2
Define user value in menu [5137]
Modbus Instance no/DeviceNet no:
43207
Profibus slot/index
169/111
EtherCAT and CANopen index (hex)
4c87
Profinet IO index
19591
Fieldbus format
UInt
Modbus format
UInt
5137
AnIn1 VaMax
Default:
0.000
Range:
-10000.000 – 10000.000
Modbus Instance no/DeviceNet no:
43551
Profibus slot/index
170/200
EtherCAT and CANopen index (hex)
4ddf
Profinet IO index
19935
Fieldbus format
Long, 1=1 rpm, 1 %, 1°
or 0.001 if Process Value/
Process Ref using a [322]
unit
Modbus format
EInt
NOTE: With AnIn Min, AnIn Max, AnIn Function Min
and AnIn Function Max settings, loss of feedback
signals (e.g. voltage drop due to long sensor wiring)
can be compensated to ensure an accurate process
control.
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......