184
CG Drives & Automation, 01-5326-01r5
The output signal can be programmed as a virtual
connection source and to the digital or relay outputs.
Communication information
Example
Create automatic RUN/STOP signal via the analogue
reference signal. Analogue current reference signal, 4-20
mA, is connected to Analogue Input 1. “AnIn1 Setup”,
menu [512] = 4-20 mA and the threshold is 4 mA. Full scale
(100%) input signal on “AnIn 1” = 20 mA. When the
reference signal on “AnIn1” increases 80% of the threshold
(4 mA x 0.8 = 3.2 mA), the AC drive will be set in RUN
mode. When the signal on “AnIn1” goes below 60% of the
threshold (4 mA x 0.6 = 2.4 mA) the AC drive is set to
STOP mode. The output of CA1 is used as a virtual
connection source that controls the virtual connection
destination RUN.
6111
CA1 Value
Default:
Speed
Process Val
0
Set by Process settings [321] and
[322]
Speed
1
rpm
Torque
2
%
Shaft Power
3
kW
El Power
4
kW
Current
5
A
Output Volt
6
V
Frequency
7
Hz
DC Voltage
8
V
IGBT Temp
9
°C
PT100_1
10
°C
PT100_2
11
°C
PT100_3
12
°C
Energy
13
kWh
Run Time
14
h
Mains Time
15
h
AnIn1
16
%
AnIn2
17
%
AnIn3
18
%
AnIn4
19
%
Process Ref
20
Set by Process settings [321] and
[322]
Process Err
21
Modbus Instance no/DeviceNet no:
43401
Profibus slot/index
170/50
EtherCAT and CANopen index (hex)
4d49
Profinet IO index
19758
Fieldbus format
UInt
Modbus format
UInt
Menu
Function
Setting
511
AnIn1 Function
Process reference
512
AnIn1 Set-up
4-20 mA, threshold is 4 mA
341
Min Speed
0
343
Max Speed
1500
6111
CA1 Value
AnIn1
6112
CA1 Level HI
16% (3.2mA/20mA x 100%)
6113
CA1 Level LO
12% (2.4mA/20mA x 100%)
6114
CA1 Type
Hysteresis
561
VIO 1 Dest
RunR
562
VIO 1 Source
CA1
215
Run/Stp Ctrl
Remote
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......