11.9.2
Status [720]
VSD Status [721]
Indicates the overall status of the AC drive.
Fig. 142 AC drive status
Example: “A/Key/Rem/TL”
This means:
A:
Parameter Set A is active.
Key:
Reference value comes from the keyboard (CP).
Rem:
Run/Stop commands come from terminals 1-22.
TL: Torque
Limit
active.
Communication information
Description of communication format
Integer values and bits used
Example:
Previous example “A/Key/Rem/TL”
is interpreted “0/1/0/4”
In bit format this is presented as
In the example above it is assumed that we have no trip or
warning condition (the alarm LED on the control panel is
off ).
Display
position
Function
Status value
1
Parameter Set
A,B,C,D
222
Source of
reference value
-Rem (remote)
-Key (keyboard)
-Com (Serial comm.)
-Opt (option)
333
Source of Run/
Stop command
-Rem (remote)
-Key (keyboard)
-Com (Serial comm.)
-Opt (option)
44
Limit functions
- - - -No limit active
-VL (Voltage Limit)
-SL (Speed Limit)
-CL (Current Limit)
-TL (Torque Limit)
Modbus Instance no/DeviceNet no:
31015
Profibus slot/index
121/159
EtherCAT and CANopen index (hex)
23f7
Profinet IO index
1015
Fieldbus format
UInt
Modbus format
UInt
721 VSD Status
Stp
1/222/333/44
Bit
Integer representation
1 - 0
Active Parameter set, where
0=A, 1=B, 2=C, 3=D
4 - 2
Source of Reference control value, where
0=Rem, 1=Key, 2=Com, 3=Option
7 - 5
Source of Run/Stop/Reset command, where
0=Rem, 1=Key, 2=Com, 3=Option
13 - 8
Active limit functions, where
0=No limit, 1=VL, 2=SL, 3=CL, 4=TL
14
Inverter is in warning (A warning condition is
active)
15
Inverter is tripped (A Trip condition is active)
Bit
Interpretation
Integer representation
0 LSB
0
A(0)
Parameter set
1
0
2
1
Key (1)
Source of control
3
0
4
0
5
0
Rem (0)
Source of
command
6
0
7
0
8
0
TL (4)
Limit functions
9
0
10
1
11
0
12
0
13
0
14
0
Warning condition
15 MSB
0
Trip condition
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......