Fig. 134
Analogue Comparator 1,
Level High [6112]
Sets the analogue comparator high level, with range
according to the selected value in menu [6111].
Min/Max setting range for menu [6112]
Communication information
No.
Description
1
The reference signal passes the Level LO value from
below (positive edge), the comparator CA1 output
stays low, mode=RUN.
2
The reference signal passes the Level HI value from
below (positive edge), the comparator CA1 output is
set high, mode=RUN.
3
The reference signal passes the threshold level of 4
mA, the motor speed will now follow the reference
signal.
T
During this period the motor speed will follow the
reference signal.
4
The reference signal reaches the threshold level, motor
speed is 0 rpm, mode = RUN.
5
The reference signal passes the Level HI value from
above (negative edge), the comparator CA1 output
stays high, mode =RUN.
6
The reference signal passes the Level LO value from
above (negative edge), the comparator CA1
output=STOP.
1 2
3
4
5
6
20 mA
4 mA
3.2 mA
2.4 mA
CA1 Level HI = 16%
CA1 Level LO = 12%
Max speed
Reference signal AnIn1
CA1
Mode
RUN
STOP
T
t
t
t
6112
CA1 Level HI
Default:
300 rpm
Range:
See min/max in table below.
Mode
Min
Max
Decimals
Process Val
Set by Process settings
[321] and [322]
3
Speed, rpm
0
Max speed
0
Torque, %
0
Max torque
0
Shaft Power, kW
0
Motor P
n
x4
0
El Power, kW
0
Motor P
n
x4
0
Current, A
0
Motor I
n
x4
1
Output volt, V
0
1000
1
Frequency, Hz
0
400
1
DC voltage, V
0
1250
1
Heatsink temp,
°
C
0
100
1
PT 100_1_2_3,
°
C
-100
300
1
Energy, kWh
0
1000000
0
Run time, h
0
65535
0
Mains time, h
0
65535
0
AnIn 1-4%
0
100
0
Process Ref
Set by Process settings
[321] and [322]
3
Process Err
Set by Process settings
[321] and [322]
3
NOTE: If Bipolar selected [6115] then Min value is
equal to -Max in the table.
Modbus Instance no/DeviceNet no:
43402
Profibus slot/index
170/51
EtherCAT and CANopen index (hex)
4d4a
Profinet IO index
19786
Fieldbus format
Long,
1=1 W, 0.1 A, 0.1 V,
0.1 Hz, 0.1
°
C, 1 kWh,
1H, 1%, 1 rpm or 0.001
via process value
Modbus format
EInt
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......