CG Drives & Automation,01-5326-01r5
175
Communication information
AnOut 1 Setup [532]
Preset scaling and offset of the output configuration.
Communication information
Fig. 131
AnOut1 Advanced [533]
With the functions in the AnOut1 Advanced menu, the
output can be completely defined according to the
application needs. The menus will automatically be adapted
to “mA” or “V”, according to the selection in “AnOut1
Setup [532]”.
AnOut1 Min [5331]
This parameter is automatically displayed if User mA or
User V is selected in menu “AnOut 1 Setup [532]”. The
menu will automatically adapt to current or voltage setting
according to the selected setup. Only visible if [532] = User
mA/V.
Communication information
Modbus Instance no/DeviceNet no:
43251
Profibus slot/index
169/155
EtherCAT and CANopen index (hex)
4cb3
Profinet IO index
19635
Fieldbus format
UInt
Modbus format
UInt
532
AnOut1 Setup
Default:
4-20mA
4–20mA
0
The current output has a fixed threshold
(Live Zero) of 4 mA and controls the full
range for the output signal. See Fig.
128.
0–20mA
1
Normal full current scale configuration of
the output that controls the full range for
the output signal. See Fig. 127.
User mA
2
The scale of the current controlled
output that controls the full range for the
output signal. Can be defined by the
advanced AnOut Min and AnOut Max
menus.
User Bipol
mA
3
Sets the output for a bipolar current
output, where the scale controls the
range for the output signal. Scale can be
defined in advanced menu AnOut Bipol.
0-10V
4
Normal full voltage scale configuration of
the output that controls the full range for
the output signal. See Fig. 127.
2–10V
5
The voltage output has a fixed threshold
(Live Zero) of 2 V and controls the full
range for the output signal. See Fig.
128.
User V
6
The scale of the voltage controlled
output that controls the full range for the
output signal. Can be defined by the
advanced AnOut Min and AnOut Max
menus.
User Bipol
V
7
Sets the output for a bipolar voltage
output, where the scale controls the
range for the output signal. Scale can be
defined in advanced menu AnOut Bipol.
Modbus Instance no/DeviceNet no:
43252
Profibus slot/index
169/156
EtherCAT and CANopen index (hex)
4cb4
Profinet IO index
19636
Fieldbus format
UInt
Modbus format
UInt
533
AnOut 1 Adv
5331
AnOut 1 Min
Default:
4 mA
Range:
0.00 – 20.00 mA, 0 – 10.00 V
Modbus Instance no/DeviceNet no:
43253
Profibus slot/index
169/157
EtherCAT and CANopen index (hex)
4cb5
Profinet IO index
19637
Fieldbus format
Long, 1=0.01 V,
0.01 mA
Modbus format
EInt
AC drive 1
Master
AC drive 2
Slave
Ref
.
AnOut
Ref.
Summary of Contents for Emotron VFX Series
Page 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 5326 01r5...
Page 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Page 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Page 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Page 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Page 218: ...216 CG Drives Automation 01 5326 01r5...
Page 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Page 236: ...234 Options CG Drives Automation 01 5326 01r5...
Page 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Page 267: ......