53
7-3. External Control (Input / Output) Interface
▣
External Control Input
Pin
No
Signal
설
명
24, 25
GND
(Input Common)
o External Input Common
16
ZERO
o It brings the Gross weight to zero
17
TARE
o It is used to weigh with the tare.
18
START
o It is used as the Start key in the batching operation
19
STOP
o It is used as the Stop key in the batching operation.
20
‘ * ‘
o It is used as the set function in SET Mode F17.
Refer to page 36.
21 ENTER
o It is used as the set function in SET Mode F18.
Refer to page 36
External Control Output
▣
The output is done according to the following condition in batching operation.
Pin
No
MODE
Output
Terms
3
ALL
Zero Band
Gross Weight
≤
S.P1(Zero band)
NORMAL
Optional preliminary
weight output
Net weight
≥
S.P4 (Final weight) – Optional preliminary weight
4
Loss-in
Optional preliminary
weight output
Gross weight
>
S.P2(Optional preliminary weight)
5
ALL
Preliminary weight
output
Net weight
≥
S.P4(Final weight) -S.P3(Preliminary weight)
6
ALL
Final weight output Net weight
≥
S.P4(Final weight) – S.P5(Free fall weight)
7
ALL High
Limit
Net weight
>
S.P4(Final weight) + S.P6(High limit weight)
8
ALL Low
Limit
Net weight
<
S.P4(Final weight) – S.P7(Low limit weight)
9
ALL
Finish
It is outputted according to Finish output time setting
10
ALL
Stable
It is outputted when the weight is stable.
11
ALL
External Output Common
Summary of Contents for NT-580A
Page 1: ...2 ...
Page 12: ...13 2 Measure of Appearance 2 1 Measure of Appearance ...
Page 24: ...25 4 4 Sealing Method Sealing Method of front cal switch ...
Page 53: ...54 External Control I O Circuit ...
Page 58: ...59 Normal Batching Diagram Loss in Weight Batching Diagram ...
Page 59: ...60 UserProgramControlMode NormalBatching ...
Page 61: ...62 UserProgramControlMode Loss in WeightBatching ...
Page 63: ...64 AutomaticProgramControlMode NormalBatching ...
Page 65: ...66 AutomaticProgramControlMode Loss in Weight Batching ...
Page 85: ...86 MEMO ...
Page 86: ...87 ...
Page 87: ...88 ...