22
CAL 3
CAL 3-1
Function : Setting Multi Calibration Range
Setting value range : 1 ~ 5
USED KEY
VFD SCREEN
DESCRIPTION
STEP- 1
Setting 1 step multi calibration
(perform CAL3-3, CAL 3-4 once)
STEP- 3
Setting 3 step multi calibration
(perform CAL3-3, CAL 3-4 three times)
▲
,
▼
: increase or decrease of
no.
▶
,
◀
: Shift of digit
”* " : Cancel and
move to CAL-1
Enter : Store and move
into next menu
STEP- 5
Setting 5step multi calibration
(perform CAL3-3, CAL 3-4 five times)
CAL 3-2
Function : Zero Calibration
USED KEY
VFD SCREEN
DESCRIPTION
UnLoAd
Empty load receptor and press “ENTER” key.
1234
Present weighing value is displayed.
Check stability, press “ENTER” key.
”* " : Cancel and
move to CAL-1
Enter : Store and move
into next menu
- - -
In the setting zero calibration..
Ref 1. After setting zero calibration without errors, it is going to automatically move to CAL 3-3 without
pressing any key
Ref 2. If zero is too low, error massage “Err 27” will be displayed.
Ref 3. If zero is too high, error massage “Err 26” will be displayed.
Summary of Contents for NT-580A
Page 1: ...2 ...
Page 12: ...13 2 Measure of Appearance 2 1 Measure of Appearance ...
Page 24: ...25 4 4 Sealing Method Sealing Method of front cal switch ...
Page 53: ...54 External Control I O Circuit ...
Page 58: ...59 Normal Batching Diagram Loss in Weight Batching Diagram ...
Page 59: ...60 UserProgramControlMode NormalBatching ...
Page 61: ...62 UserProgramControlMode Loss in WeightBatching ...
Page 63: ...64 AutomaticProgramControlMode NormalBatching ...
Page 65: ...66 AutomaticProgramControlMode Loss in Weight Batching ...
Page 85: ...86 MEMO ...
Page 86: ...87 ...
Page 87: ...88 ...