136
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS
*The display text changes depending on the remote switch configuration (
Configuration
→
UNIT
→
RM.CF
). If
RM.CF
is set to 0 (No Remote Switch), then the display
text will be “On” or “Off.” If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If
RM.CF
is set to 2 (Start/Stop),
then the display text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
GEN.I
GENERAL INPUTS
→
FLT.S
Filter Status Input
DRTY/CLN
FLTS
forcible
→
G.FAN
Fan Request From IGC
ON/OFF
IGCFAN
→
REMT
Remote Input State
*
RMTIN
forcible
→
ENTH
Enth. Switch Read High ?
YES/NO
ENTH
forcible
→
S.FN.S
Supply Fan Status Switch
ON/OFF
SFS
forcible
→
FRZ.S
Freeze Status Switch
ALRM/NORM
FRZ
forcible
→
PP.SW
Plenum Press.Safety Sw.
HIGH/LOW
PPS
forcible
→
DL.S1
Demand Limit Switch 1
ON/OFF
DMD_SW1
forcible
→
DL.S2
Demand Limit Switch 2
ON/OFF
DMD_SW2
forcible
→
DH.IN
Dehumidify Switch Input
ON/OFF
DHDISCIN
forcible
FD.BK
COMPRESSOR FEEDBACK
→
HPS.A
Circ A High Press. Switch
HIGH/LOW
CIRCAHPS
→
HPS.B
Circ B High Press. Switch
HIGH/LOW
CIRCBHPS
→
CS.A1
Compressor A1 Feedback
ON/OFF
CSB_A1
→
CS.A2
Compressor A2 Feedback
ON/OFF
CSB_A2
→
CS.B1
Compressor B1 Feedback
ON/OFF
CSB_B1
→
CS.B2
Compressor B2 Feedback
ON/OFF
CSB_B2
STAT
THERMOSTAT INPUTS
→
G
Thermostat G Input
ON/OFF
G
forcible
→
W1
Thermostat W1 Input
ON/OFF
W1
forcible
→
W2
Thermostat W2 Input
ON/OFF
W2
forcible
→
Y1
Thermostat Y1 Input
ON/OFF
Y1
forcible
→
Y2
Thermostat Y2 Input
ON/OFF
Y2
forcible
FIRE
FIRE-SMOKE INPUTS
→
FSD
Fire Shutdown Input
ALRM/NORM
FSD
forcible
→
PRES
Pressurization Input
ALRM/NORM
PRES
forcible
→
EVAC
Evacuation Input
ALRM/NORM
EVAC
forcible
→
PURG
Smoke Purge Input
ALRM/NORM
PURG
forcible
REL.H
RELATIVE HUMIDITY
→
OA.RH
Outside Air Rel. Humidity
%
OARH
forcible
→
OA.EN
Outdoor Air Enthalpy
OAE
→
OA.DP
OutsideAir Dewpoint Temp
dF
OADEWTMP
→
RA.RH
Return Air Rel. Humidity
%
RARH
forcible
→
RA.EN
Return Air Enthalpy
RAE
→
SP.RH
Space Relative Humidity
%
SPRH
forcible
→
SP.EN
Space Enthalpy
SPE
AIR.Q
AIR QUALITY SENSORS
→
IAQ.I
IAQ - Discrete Input
HIGH/LOW
IAQIN
forcible
→
IAQ
IAQ - PPM Return CO2
IAQ
forcible
→
OAQ
OAQ - PPM Return CO2
OAQ
forcible
→
DAQ
Diff.Air Quality in PPM
DAQ
→
IQ.P.O
IAQ Min.Pos. Override
%
IAQMINOV
forcible
CFM
CFM SENSORS
→
O.CFM
Outside Air CFM
CFM
OACFM
→
R.CFM
Return Air CFM
CFM
RACFM
→
S.CFM
Supply Air CFM
CFM
SACFM
→
D.CFM
Fan Track Control D.CFM
CFM
DELTACFM
RSET
RESET INPUTS
→
SA.S.R
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
→
SP.RS
Static Pressure Reset
SPRESET
forcible
4-20
4-20 MILLIAMP INPUTS
→
IAQ.M
IAQ Milliamps
ma
IAQ_MA
→
OAQ.M
OAQ Milliamps
ma
OAQ_MA
→
SP.R.M
SP Reset milliamps
ma
SPRST_MA
→
DML.M
4-20 ma Demand Signal
ma
DMDLMTMA
forcible
→
EDR.M
EDT Reset Milliamps
ma
EDTRESMA
→
ORH.M
OARH Milliamps
ma
OARH_MA
→
SRH.M
SPRH Milliamps
ma
SPRH_MA
→
RRH.M
RARH Milliamps
ma
RARH_MA
→
SAC.M
SACFM Milliamps
ma
SACFM_MA
→
SA.M.T
Supply Air CFM Trim (ma)
-2.0
→
2.0
SAMATRIM
→
RAC.M
RACFM Milliamps
ma
RACFM_MA
→
RA.M.T
Return Air CFM Trim (ma)
-2.0
→
2.0
RAMATRIM
config
→
OAC.M
OACFM Milliamps
ma
OACFM_MA
→
OA.M.T
Outside Air CFM Trim(ma)
-2.0
→
2.0
OAMATRIM
config
→
BP.M
BP Milliamps
ma
BP_MA
→
BP.M.T
Bldg. Pressure Trim (ma)
-2.0
→
2.0
BPMATRIM
config
→
SP.M
SP Milliamps
ma
SP_MA
→
SP.M.T
Static Press. Trim (ma)
-2.0
→
2.0
SPMATRIM
config
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...