APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — OUTPUTS
MODE — CONFIGURATION
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
FANS
FANS
→
S.FAN
Supply Fan Relay
ON/OFF
SFAN
→
S.VFD
Supply Fan VFD Speed
0-100
%
SFAN_VFD
→
E.VFD
Exhaust Fan VFD Speed
0-100
%
EFAN_VFD
→
P.E.1
Power Exhaust Relay 1
ON/OFF
PE1
→
P.E.2
Power Exhaust Relay 2
ON/OFF
PE2
→
CD.F.A
Condenser Fan Circuit A
ON/OFF
CONDFANA
→
CD.F.B
Condenser Fan Circuit B
ON/OFF
CONDFANB
→
CD.MM
Motormaster Condensr Fan
ON/OFF
PULSCFAB
COOL
COOLING
→
A1
Compressor A1 Relay
ON/OFF
CMPA1
→
U1.A1
Unloader 1 - Comp A1
ON/OFF
UNL_1_A1
→
U2.A1
Unloader 2 - Comp A1
ON/OFF
UNL_2_A1
→
A2
Compressor A2 Relay
ON/OFF
CMPA2
→
B1
Compressor B1 Relay
ON/OFF
CMPB1
→
U1.B1
Unloader 1 - Comp B1
ON/OFF
UNL_1_B1
→
U2.B1
Unloader 2 - Comp B1
ON/OFF
UNL_2_B1
→
B2
Compressor B2 Relay
ON/OFF
CMPB2
HEAT
HEATING
→
HT.1
Heat Relay 1
ON/OFF
HS1
→
HT.2
Heat Relay 2
ON/OFF
HS2
→
HT.3
Relay 3 W1 Gas Valve 2
ON/OFF
HS3
→
HT.4
Relay 4 W2 Gas Valve 2
ON/OFF
HS4
→
HT.5
Relay 5 W1 Gas Valve 3
ON/OFF
HS5
→
HT.6
Relay 6 W2 Gas Valve 3
ON/OFF
HS6
→
H.I.R
Heat Interlock Relay
ON/OFF
HIR
forcible
→
HTC.P
Ht.Coil Act.Current Pos.
0-100
%
HTCLRPOS
ACTU
ACTUATORS
→
ECN.P
Economizer Act.Curr.Pos.
0-100
%
ECONRPOS
→
EC2.P
Economzr 2 Act.Curr.Pos.
0-100
%
ECON2POS
→
ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOCMD
forcible
→
IGV.P
IGV Actuator Current Pos
0-100
%
IGV_RPOS
→
IGV.C
IGV Actuator Command Pos
0-100
%
IGV_CPOS
→
BP1.P
BP 1 Actuator Curr.Pos.
0-100
%
BP1_RPOS
→
BP1.C
BP 1 Command Position
0-100
%
BP1_CPOS
→
BP2.P
BP 2 Actuator Curr.Pos.
0-100
%
BP2_RPOS
→
BP2.C
BP 2 Command Position
0-100
%
BP2_CPOS
→
HTC.P
Ht.Coil Act.Current Pos.
0-100
%
HTCLRPOS
→
HTC.C
Ht.Coil Command Position
0-100
%
HTCLCPOS
→
HMD.P
Humidifier Act.Curr.Pos.
0-100
%
HUMDRPOS
→
HMD.C
Humidifier Command Pos.
0-100
%
HUMDCPOS
GEN.O
GENERAL OUTPUTS
→
HUM.R
Humidifier Relay
ON/OFF
HUMIDRLY
→
ALRM
Remote Alarm / Aux Relay
ON/OFF
ALRM
forcible
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
UNIT
UNIT CONFIGURATION
→
C.TYP
Machine Control Type
1 - 6 (multi-text strings)
CTRLTYPE
4
42,44
→
CV.FN
Fan Mode (0=Auto, 1=Cont)
0 - 1 (multi-text strings)
FAN_MODE
1
44
→
RM.CF
Remote Switch Config
0 - 3 (multi-text strings)
RMTINCFG
0
44
→
CEM
CEM Module Installed
Yes/No
CEM_BRD
No
44
→
TCS.C
Temp.Cmp.Strt.Cool Factr
0 - 60
min
TCSTCOOL
0
44
→
TCS.H
Temp.Cmp.Strt.Heat Factr
0 - 60
min
TCSTHEAT
0
44
→
SFS.S
Fan Fail Shuts Down Unit
Yes/No
SFS_SHUT
No
44
→
SFS.M
Fan Stat Monitoring Type
0 - 2 (multi-text strings)
SFS_MON
0
44
→
VAV.S
VAV Unocc.Fan Retry Time
0 - 720
min
SAMPMINS
50
44
→
SIZE
Unit Size (30-105)
30 - 105
UNITSIZE
30
44
→
50.HZ
50 Hertz Unit ?
Yes/No
UNIT_HZ
No
44,45
→
MAT.S
MAT Calc Config
0 - 2 (multi-text strings)
MAT_SEL
1
44,45
→
MAT.R
Reset MAT Table Entries?
Yes/No
MATRESET
No
44,45
→
MAT.D
MAT Outside Air Default
0 -100
%
MATOAPOS
20
44,45
→
ALTI
Altitude……..in feet:
0 - 60000
ALTITUDE
0
44,45
→
DLAY
Startup Delay Time
0 -900
secs
DELAY
0
→
AUX.R
Auxiliary Relay Config
0 - 3 (multi-text strings)
AUXRELAY
0
→
SENS
INPUT SENSOR CONFIG
→
SENS
→
SPT.S
Space Temp Sensor
Enable/Disable
SPTSENS
Disable
44,45
→
SENS
→
SP.O.S
Space Temp Offset Sensor
Enable/Disable
SPTOSENS
Disable
44,45
→
SENS
→
SP.O.R
Space Temp Offset Range
1 - 10
SPTO_RNG
5
44,45
→
SENS
→
SRH.S
Space Air RH Sensor
Enable/Disable
SPRHSENS
Disable
44,45
→
SENS
→
RRH.S
Return Air RH Sensor
Enable/Disable
RARHSENS
Disable
44,45
→
SENS
→
FLT.S
Filter Stat.Sw.Enabled ?
Enable/Disable
FLTS_ENA
Disable
44,45
COOL
COOLING CONFIGURATION
→
Z.GN
Capacity Threshold Adjst
-10 - 10
Z_GAIN
1
46,47
→
MC.LO
Compressor Lockout Temp
-25 - 55
dF
OATLCOMP
40
46,47
→
L.L.EN
Lead/Lag Operation ?
Yes/No
LLENABLE
No
46,47
→
M.M.
Motor Master Control ?
Yes/No
MOTRMAST
No
46,47
→
HPSP
Head Pressure Setpoint
80 - 150
dF
HPSP
113
46,47
→
A1.EN
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
46,47
→
A2.EN
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
46,47
→
B1.EN
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
46,47
→
B2.EN
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
46,47
→
CS.A1
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
46,47
→
CS.A2
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
47
→
CS.B1
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
47
→
CS.B2
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
47
→
HPS.A
CMPA1 Hi.Pr.Sw. Trip
365 - 415
PSIG
HPSATRIP
415
47
→
HPS.B
CMPB1 Hi.Pr.Sw. Trip
365 - 415
PSIG
HPSBTRIP
415
47
→
H.SST
Hi SST Alert Delay Time
5 - 30
min
HSSTTIME
10
47
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...