APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
COMPRESR (cont)
Enable Compressor B1
Enable/Disable
CMPB1ENA
config
Compressor B2 Relay
On/Off
CMPB2
Compressor B2 Feedback
On/Off
CSB_B2
Curr.Sens.Brd. B2 Status
ascii
CSBB2ASC
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
config
Comp B2 Locked Out ?
Yes/No
CMPB2LOK
Compressor B2 Strikes
CMPB2STR
Enable Compressor B2
Enable/Disable
CMPB2ENA
config
COMPTRIP
Comp. Security Password
0-10000
COMPPASS
config
Low SP Circ.A Trip 48.0
LSPATRIP
config
Low SP Circ.B Trip 48.0
LSPBTRIP
config
MOP 1/3 Lo SP Trip 28.0
PSIG
SP13L_T
config
MOP 1/3 Lo DP Trip 242.7
PSIG
DP13L_T
config
MOP 1/3 Hi SP Trip 75.0
PSIG
SP13H_T
config
MOP 1/3 Hi DP Trip 430.0
PSIG
DP13H_T
config
MOP 1/3 Mm DP Trip 3.985
DP13Mm_T
config
MOP 1/3 Mb DP Tr 131.117
DP13Mb_T
config
MOP 1/2 Lo SP Trip 28.0
PSIG
SP12L_T
config
MOP 1/2 Lo DP Trip 242.7
PSIG
DP12L_T
config
MOP 1/2 Hi SP Trip 61.5
PSIG
SP12H_T
config
MOP 1/2 Hi DP Trip 430.0
PSIG
DP12H_T
config
MOP 1/2 Mm DP Trip 5.591
DP12Mm_T
config
MOP 1/2 Mb DP Trp 156.55
DP12Mb_T
config
MOP 2/3 Lo SP Trip 28.0
PSIG
SP23L_T
config
MOP 2/3 Lo DP Trip 316.2
PSIG
DP23L_T
config
MOP 2/3 Hi SP Trip 57.4
PSIG
SP23H_T
config
MOP 2/3 Hi DP Trip 430.0
PSIG
DP23H_T
config
MOP 2/3 Mm DP Trip 3.871
DP23Mm_T
config
MOP 2/3 Mb DP Trp 207.82
DP23Mb_T
config
MOP Ful Lo SP Trip 28.0
PSIG
SPFLL_T
config
MOP Ful Lo DP Trip 340.0
PSIG
DPFLL_T
config
MOP Ful Hi SP Trip 52.4
PSIG
SPFLH_T
config
MOP Ful Hi DP Trip 430.0
PSIG
DPFLH_T
config
MOP Ful Mm DP Trip 3.689
DPFLMm_T
config
MOP Ful Mb DP Trp 103.28
DPFLMb_T
config
DMANDLIM
Active Demand Limit
0-100
%
DEM_LIM
forcible
Percent Total Capacity
0-100
%
CAPTOTAL
Demand Limit Select
0-3
DMD_CTRL
config
Demand Limit Switch 1
On/Off
DMD_SW1
forcible
Demand Limit Switch 2
On/Off
DMD_SW2
forcible
Demand Limit Sw.1 Setpt.
0-100
%
DLSWSP1
config
Demand Limit Sw.2 Setpt.
0-100
%
DLSWSP2
config
4-20 ma Demand Signal
4-20
ma
DMDLMTMA
forcible
Demand Limit at 20 ma
0-100
%
DMT20MA
config
CCN Loadshed Signal
0-99
DL_STAT
Loadshed Group Number
0-99
SHED_NUM
config
Loadshed Demand Delta
0-60
%
SHED_DEL
config
Maximum Loadshed Time
0-120
min
SHED_TIM
config
ECON_MIN
Economizer Act.Cmd.Pos.
%
ECONOCMD
forcible
Economizer Act.Curr.Pos.
%
ECONOPOS
Economzr 2 Act.Curr.Pos.
%
ECON2POS
Econo Current Min. Pos.
%
ECMINPOS
Econo Current Min. CFM
CFM
ECMINCFM
Outside Air CFM
CFM
OACFM
Diff.Air Quality in PPM
DAQ
IAQ Min.Pos.Override
%
IAQMINOV
forcible
Econ Remote 10K Pot Val.
ECON_POT
forcible
IAQ - PPM Return CO2
IAQ
forcible
OAQ - PPM Return CO2
OAQ
forcible
IAQ - Discrete Input
IAQIN
forcible
IAQ Demand Vent Min.Pos.
%
IAQMINP
config
Economizer Min.Position
%
ECONOMIN
config
IAQ Demand Vent Min.Flow
CFM
OACFMMIN
config
Economizer Min.Flow
CFM
OACFMMAX
config
Econ OACFM MinPos Deadbd
CFM
OACFM_DB
config
IAQ Analog Sensor Config
IAQANCFG
config
IAQ 4-20 ma Fan Config
IAQANFAN
config
IAQ Discrete Input Confg
IAQINCFG
config
IAQ Disc.In. Fan Config
IAQINFAN
config
IAQ Econo Override Pos.
%
IAQOVPOS
config
Diff.Air Quality LoLimit
DAQ_LOW
config
Diff.Air Quality HiLimit
DAQ_HIGH
config
DAQ PPM Fan Off Setpoint
DAQFNOFF
config
DAQ PPM Fan On Setpoint
DAQFNON
config
Diff. AQ Responsiveness
IAQREACT
config
IAQ Low Reference
IAQREFL
config
IAQ High Reference
IAQREFH
config
OAQ Lockout Value
OAQLOCK
config
OAQ 4-20ma Sensor Config
ma
OAQANCFG
config
IAQ milliamps
ma
IAQ_MA
OAQ milliamps
OAQ_MA
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...