APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
BP
BUILDING PRESS. CONFIGS
→
BP.CF
Building Press. Config
0 - 5 (multi-text strings)
BLDG_CFG
0
70,71
→
BP.S
Building Pressure Sensor
Enable/Disable
BPSENS
Disable
70,71
→
BP.R
Bldg. Press. (+/-) Range
0.10 - 0.25
"H2O
BP_RANGE
0.25
70,71
→
BP.SP
Building Pressure Setp.
-0.25 - 0.25
"H2O
BPSP
0.05
70,71
→
BP.SO
BP Setpoint Offset
0 - 0.5
"H2O
BPSO
0.05
70,71
→
BP.P1
Power Exhaust On Setp.1
0 - 100
%
PES1
25
70,71
→
BP.P2
Power Exhaust On Setp.2
0 - 100
%
PES2
75
70,71
→
B.V.A
VFD/ACTUATOR CONFIG
→
B.V.A
→
BP.FS
VFD/Act. Fire Speed/Pos.
0 - 100
%
BLDGPFSO
100
70,71
→
B.V.A
→
BP.MN
VFD/Act. Min.Speed/Pos.
0 - 50
%
BLDGPMIN
0
70,71
→
B.V.A
→
BP.MX
VFD Maximum Speed
50 - 100
%
BLDGPMAX
100
70,71
→
B.V.A
→
BP.1M
BP 1 Actuator Max Pos.
85 - 100
%
BP1SETMX
100
70,71
→
B.V.A
→
BP.2M
BP 2 Actuator Max Pos.
85 - 100
%
BP2SETMX
100
70,71
→
B.V.A
→
BP.CL
BP Hi Cap VFD Clamp Val.
5 - 25
%
BLDGCLMP
10
70,71
→
FAN.T
FAN TRACKING CONFIG
→
FAN.T
→
FT.CF
Fan Track Learn Enable
Yes/No
DCFM_CFG
No
70,71
→
FAN.T
→
FT.TM
Fan Track Learn Rate
5-60
min
DCFMRATE
15
70,71
→
FAN.T
→
FT.ST
Fan Track Initial DCFM
-20000 - 20000
CFM
DCFMSTRT
2000
70,71
→
FAN.T
→
FT.MX
Fan Track Max Clamp
0 - 20000
CFM
DCFM_MAX
4000
70,71
→
FAN.T
→
FT.AD
Fan Track Max Correction
0 -20000
CFM
DCFM_ADJ
1000
70,71
→
FAN.T
→
FT.OF
Fan Track Internl EEPROM
-20000 - 20000
CFM
DCFM_OFF
0
70,71
→
FAN.T
→
FT.RM
Fan Track Internal RAM
-20000 - 20000
CFM
DCFM_RAM
0
70,71
→
FAN.T
→
FT.RS
Fan Track Reset Internal
Yes/No
DCFMRSET
No
70,71
→
FAN.T
→
SCF.C
Supply Air CFM Config
1 - 2 (multi-text strings)
SCFM_CFG
1
70,71
→
B.PID
BLDG.PRESS.PID CONFIGS
→
B.PID
→
BP.TM
Bldg.Pres.PID Run Rate
5 - 120
sec
BPIDRATE
10
70,71
→
B.PID
→
BP.P
Bldg.Press. Prop. Gain
0 - 5
BLDGP_PG
0.5
70,71
→
B.PID
→
BP.I
Bldg.Press. Integ. Gain
0 - 2
BLDGP_IG
0.5
70,71
→
B.PID
→
BP.D
Bldg.Press. Deriv. Gain
0 - 5
BLDGP_DG
0.3
70,71
→
ACT.C
BLDG.PRES. ACTUATOR CFGS
→
ACT.C
→
BP.1
BLDG.PRES. ACT.1 CONFIGS
→
ACT.C
→
BP.1
→
SN.1
BP 1 Serial Number 1
0 - 255
BP_1_SN1
0
70-72
→
ACT.C
→
BP.1
→
SN.2
BP 1 Serial Number 2
0 - 255
BP_1_SN2
0
70-72
→
ACT.C
→
BP.1
→
SN.3
BP 1 Serial Number 3
0 - 255
BP_1_SN3
0
70-72
→
ACT.C
→
BP.1
→
SN.4
BP 1 Serial Number 4
0 - 255
BP_1_SN4
0
70-72
→
ACT.C
→
BP.1
→
SN.5
BP 1 Serial Number 5
0 - 255
BP_1_SN5
0
70-72
→
ACT.C
→
BP.1
→
C.A.LM
BP1 Cntrl Angle Lo Limit
0-90
BP1_CALM
35
70-72
→
ACT.C
→
BP.2
BLDG.PRES. ACT.2 CONFIGS
→
ACT.C
→
BP.2
→
SN.1
BP 2 Serial Number 1
0 - 255
BP_2_SN1
0
70-72
→
ACT.C
→
BP.2
→
SN.2
BP 2 Serial Number 2
0 - 255
BP_2_SN2
0
70-72
→
ACT.C
→
BP.2
→
SN.3
BP 2 Serial Number 3
0 - 255
BP_2_SN3
0
70-72
→
ACT.C
→
BP.2
→
SN.4
BP 2 Serial Number 4
0 - 255
BP_2_SN4
0
70-72
→
ACT.C
→
BP.2
→
SN.5
BP 2 Serial Number 5
0 - 255
BP_2_SN5
0
70-72
→
ACT.C
→
BP.2
→
C.A.LM
BP2 Cntrl Angle Lo Limit
0-90
BP2_CALM
35
70-72
D.LV.T
COOL/HEAT SETPT. OFFSETS
→
L.H.ON
Dmd Level Lo Heat On
-1 - 2
^F
DMDLHON
1.5
48,55,56
→
H.H.ON
Dmd Level(+) Hi Heat On
0.5 - 20.0
^F
DMDHHON
0.5
48,55,56
→
L.H.OF
Dmd Level(-) Lo Heat Off
0.5 - 2.0
^F
DMDLHOFF
1
48,55,56
→
L.C.ON
Dmd Level Lo Cool On
-1 - 2
^F
DMDLCON
1.5
48,49,55
→
H.C.ON
Dmd Level(+) Hi Cool On
0.5 - 20.0
^F
DMDHCON
0.5
48,49,55
→
L.C.OF
Dmd Level(-) Lo Cool Off
0.5 - 2.0
^F
DMDLCOFF
1
48,49,55
→
C.T.LV
Cool Trend Demand Level
0.1 - 5.0
^F
CTRENDLV
0.1
48,49,55
→
H.T.LV
Heat Trend Demand Level
0.1 - 5.0
^F
HTRENDLV
0.1
48,55,56
→
C.T.TM
Cool Trend Time
30 - 600
sec
CTRENDTM
120
48,49,55
→
H.T.TM
Heat Trend Time
30 - 600
sec
HTRENDTM
120
48,55,56
DMD.L
DEMAND LIMIT CONFIG.
→
DM.L.S
Demand Limit Select
0 - 3 (multi-text strings)
DMD_CTRL
0
52,53
→
D.L.20
Demand Limit at 20 ma
0 - 100
%
DMT20MA
100
53
→
SH.NM
Loadshed Group Number
0 - 99
SHED_NUM
0
53
→
SH.DL
Loadshed Demand Delta
0 - 60
%
SHED_DEL
0
53
→
SH.TM
Maximum Loadshed Time
0 - 120
min
SHED_TIM
60
53
→
D.L.S1
Demand Limit Sw.1 Setpt.
0 - 100
%
DLSWSP1
80
53
→
D.L.S2
Demand Limit Sw.2 Setpt.
0 - 100
%
DLSWSP2
50
53
IAQ
INDOOR AIR QUALITY CFG.
→
DCV.C
DCV ECONOMIZER SETPOINTS
→
DCV.C
→
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
74-76
→
DCV.C
→
IAQ.M
IAQ Demand Vent Min.Pos.
0 - 100
%
IAQMINP
0
74,75
→
DCV.C
→
O.C.MX
Economizer Min.Flow
0 - 20000
CFM
OACFMMAX
2000
74
→
DCV.C
→
O.C.MN
IAQ Demand Vent Min.Flow
0 - 20000
CFM
OACFMMIN
0
74
→
DCV.C
→
O.C.DB
Econ.Min.Flow Deadband
200 - 1000
CFM
OACFM_DB
400
74
→
AQ.CF
AIR QUALITY CONFIGS
→
AQ.CF
→
IQ.A.C
IAQ Analog Sensor Config
0 - 4 (multi-text strings)
IAQANCFG
0
74
→
AQ.CF
→
IQ.A.F
IAQ 4-20 ma Fan Config
0 - 2 (multi-text strings)
IAQANFAN
0
74
→
AQ.CF
→
IQ.I.C
IAQ Discrete Input Config
0 - 2 (multi-text strings)
IAQINCFG
0
74,75
→
AQ.CF
→
IQ.I.F
IAQ Disc.In. Fan Config
0 - 2 (multi-text strings)
IAQINFAN
0
74,75
→
AQ.CF
→
OQ.A.C
OAQ 4-20ma Sensor Config
0 - 2 (multi-text strings)
OAQANCFG
0
74,75
→
AQ.SP
AIR QUALITY SETPOINTS
→
AQ.SP
→
IQ.O.P
IAQ Econo Override Pos.
0 - 100
%
IAQOVPOS
100
74,75
→
AQ.SP
→
IQ.O.C
IAQ Override Flow
0 - 31000
CFM
IAQOVCFM
10000
74
→
AQ.SP
→
DAQ.L
Diff.Air Quality LoLimit
0 - 1000
DAQ_LOW
100
74-76
→
AQ.SP
→
DAQ.H
Diff. Air Quality HiLimit
100 - 2000
DAQ_HIGH
700
74-76
→
AQ.SP
→
D.F.OF
DAQ PPM Fan Off Setpoint
0 - 2000
DAQFNOFF
200
74,75
→
AQ.SP
→
D.F.ON
DAQ PPM Fan On Setpoint
0 - 2000
DAQFNON
400
74,75
→
AQ.SP
→
IAQ.R
Diff. AQ Responsiveness
-5 - 5
IAQREACT
0
74,76
→
AQ.SP
→
OAQ.L
OAQ Lockout Value
0 - 2000
OAQLOCK
0
74,75
→
AQ.SP
→
OAQ.U
User Determined OAQ
0 - 5000
OAQ_USER
400
74
→
AQ.S.R
AIR QUALITY SENSOR RANGE
→
AQ.S.R
→
IQ.R.L
IAQ Low Reference
0 - 5000
IAQREFL
0
74,75
→
AQ.S.R
→
IQ.R.H
IAQ High Reference
0 - 5000
IAQREFH
2000
74,75
→
AQ.S.R
→
OQ.R.L
OAQ Low Reference
0 - 5000
OAQREFL
0
74,76
→
AQ.S.R
→
OQ.R.H
OAQ High Reference
0 - 5000
OAQREFH
2000
74,76
→
IAQ.P
IAQ PRE-OCCUPIED PURGE
→
IAQ.P
→
IQ.PG
IAQ Purge
Yes/No
IAQPURGE
No
74,76
→
IAQ.P
→
IQ.P.T
IAQ Purge Duration
5 - 60
min
IAQPTIME
15
74,76
→
IAQ.P
→
IQ.P.L
IAQ Purge LoTemp Min Pos
0 - 100
%
IAQPLTMP
10
74,76
→
IAQ.P
→
IQ.P.H
IAQ Purge HiTemp Min Pos
0 - 100
%
IAQPHTMP
35
74,76
→
IAQ.P
→
IQ.L.O
IAQ Purge OAT Lockout
35 - 70
dF
IAQPNTLO
50
74,76
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...