APPENDIX B — CCN TABLES (cont)
TIME SCHEDULE CONFIG TABLE
Allowable Entries: Day not selected = 0 Day selected = 1
APPENDIX C — UNIT STAGING TABLES
STAGING SEQUENCE — SIZE 030 UNITS — 60 Hz
LEGEND
STAGING SEQUENCE — SIZE 030 UNITS — 50 Hz
LEGEND
STAGING SEQUENCE — SIZE 035 UNITS
LEGEND
DAY FLAGS
MTWTFSSH
OCCUPIED
TIME
UNOCCUPIED
TIME
Period 1:
00000000
00:00
00:00
Period 2:
00000000
00:00
00:00
Period 3:
00000000
00:00
00:00
Period 4:
00000000
00:00
00:00
Period 5:
00000000
00:00
00:00
Period 6:
00000000
00:00
00:00
Period 7:
00000000
00:00
00:00
Period 8:
00000000
00:00
00:00
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
1
0
0
0
0
0
16%
2
1
1
0
0
0
0
0
0
32%
3
1
0
0
0
0
0
0
0
50%
4
1
0
0
0
1
1
1
0
66%
5
1
0
0
0
1
1
0
0
82%
6
1
0
0
0
1
0
0
0
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
1
0
16%
2
0
0
0
0
1
1
0
0
32%
3
0
0
0
0
1
0
0
0
50%
4
1
1
1
0
1
0
0
0
66%
5
1
1
0
0
1
0
0
0
82%
6
1
0
0
0
1
0
0
0
100%
0 —
Off
a,b —
Compressor Circuit Designation
1 —
On
u
—
Unloader
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
0
0
0
0
0
0
29%
2
1
1
0
0
1
1
1
0
43%
3
1
1
0
0
1
1
0
0
57%
4
1
0
0
0
1
1
1
0
71%
5
1
0
0
0
1
1
0
0
85%
6
1
0
0
0
1
0
0
0
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
1
0
14%
2
0
0
0
0
1
1
0
0
28%
3
1
1
0
0
1
1
1
0
43%
4
1
1
0
0
1
1
0
0
57%
5
1
0
0
0
1
1
1
0
71%
6
1
0
0
0
1
1
0
0
85%
7
1
0
0
0
1
0
0
0
100%
0 —
Off
a,b —
Compressor Circuit Designation
1 —
On
u
—
Unloader
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
1
0
0
0
0
0
14%
2
1
1
0
0
0
0
0
0
28%
3
1
1
1
0
1
1
0
0
43%
4
1
1
0
0
1
1
0
0
57%
5
1
1
1
0
1
0
0
0
71%
6
1
1
0
0
1
0
0
0
85%
7
1
0
0
0
1
0
0
0
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
0
0
29%
2
1
1
1
0
1
1
0
0
43%
3
1
1
0
0
1
1
0
0
57%
4
1
1
1
0
1
0
0
0
71%
5
1
1
0
0
1
0
0
0
85%
6
1
0
0
0
1
0
0
0
100%
0 —
Off
a,b —
Compressor Circuit Designation
1 —
On
u
—
Unloader
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...