Table 21 — Fan Performance — 48ZG,ZN,ZT,ZW,Z6,Z8 and 50ZG,ZN,ZT,ZW,ZX,ZZ,Z2,Z3,Z6,Z7,Z8,Z9105
Units With Forward-Curved Fan*
LEGEND
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Table 30C.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. For return fan (48Z6,Z8 and 50Z6,Z7,Z8,Z9) and high-capacity
power exhaust (48ZT,ZW and 50ZT,ZW,ZX,ZZ) units, add com-
ponent pressure drop for economizer. Do not add component
pressure drop for power exhaust.
3. See Table 30C before using Fan Performance tables.
4. Conversion — Bhp to kW:
See Tables 26-28 for motor efficiency.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0 1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
20,000
275
5.83
301
6.82
324
7.81
346
8.82
366
9.86
386
10.94
406
12.05
425
13.20
22,000
298
7.53
321
8.62
343
9.70
364
10.80
383
11.92
402
13.07
420
14.25
438
15.46
24,000
320
9.55
342
10.75
363
11.93
383
13.11
401
14.31
419
15.54
436
16.79
453
18.07
26,000
343
11.91
364
13.22
384
14.50
402
15.78
420
17.07
437
18.37
453
19.70
469
21.05
28,000
367
14.65
386
16.06
405
17.45
422
18.83
439
20.20
455
21.59
471
23.00
486
24.43
30,000
390
17.78
408
19.31
426
20.80
443
22.28
459
23.75
474
25.24
489
26.73
504
28.24
32,000
414
21.36
431
22.99
448
24.59
464
26.17
479
27.75
494
29.32
508
30.90
523
32.49
34,000
437
25.39
454
27.13
470
28.84
485
30.53
500
32.20
514
33.87
528
35.55
542
37.23
36,000
461
29.92
477
31.77
492
33.58
506
35.38
521
37.16
534
38.93
548
40.69
561
42.47
38,000
485
34.96
500
36.91
514
38.85
528
40.74
542
42.63
555
44.50
568
46.36
581
48.23
40,000
509
40.54
523
42.61
537
44.65
550
46.66
563
48.64
576
50.62
589
52.59
601
54.56
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
2.4
2.6
2.8
3.0 3.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
20,000
443
14.38
460
15.58
478
16.82
495
18.07
511
19.35
527
20.65
543
21.98
559
23.32
22,000
455
16.70
472
17.98
489
19.28
505
20.60
521
21.96
536
23.33
551
24.72
566
26.14
24,000
470
19.38
486
20.72
501
22.08
517
23.48
532
24.89
547
26.34
561
27.80
576
29.29
26,000
485
22.43
500
23.83
515
25.27
530
26.73
544
28.22
559
29.72
573
31.26
586
32.81
28,000
501
25.89
516
27.36
530
28.86
544
30.38
558
31.94
572
33.51
585
35.11
599
36.74
30,000
518
29.76
533
31.32
546
32.89
560
34.48
573
36.10
586
37.74
599
39.41
612
41.11
32,000
536
34.11
550
35.73
563
37.38
576
39.04
589
40.73
601
42.45
614
44.18
626
45.94
34,000
555
38.92
568
40.63
581
42.36
593
44.10
605
45.87
618
47.64
630
49.45
641
51.27
36,000
574
44.25
586
46.03
599
47.85
611
49.67
623
51.51
634
53.37
646
55.25
657
57.14
38,000
593
50.10
605
51.98
617
53.87
629
55.77
640
57.71
652
59.63
663
61.59
674
63.54
40,000
613
56.52
625
58.49
636
60.48
648
62.46
659
64.47
—
—
—
—
—
—
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.4
3.6
3.8
4.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
20,000
574
24.68
589
26.06
604
27.45
618
28.86
22,000
581
27.57
596
29.04
610
30.51
624
31.99
24,000
590
30.80
604
32.33
617
33.88
631
35.44
26,000
600
34.39
613
35.99
627
37.61
640
39.24
28,000
612
38.38
624
40.05
637
41.74
650
43.44
30,000
624
42.81
637
44.54
649
46.29
661
48.06
32,000
638
47.72
650
49.51
662
51.33
674
53.17
34,000
653
53.12
665
54.98
676
56.87
—
—
36,000
669
59.06
680
60.98
—
—
—
—
38,000
—
—
—
—
—
—
—
—
40,000
—
—
—
—
—
—
—
—
48/50ZN,ZW,ZZ,Z3,Z8,Z9 units only.
Bhp —
Brake Horsepower
Kilowatts =
Bhp x .746
Motor efficiency
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...