APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
DEFAULT
BP__ (cont)
Bldg.Pres.PID Run Rate
5 - 120
sec
BPIDRATE
10
Bldg.Press. Prop. Gain
0 - 5
BLDGP_PG
1
Bldg.Press. Integ. Gain
0 - 2
BLDGP_IG
1
Bldg.Press. Deriv. Gain
0 - 5
BLDGP_DG
0.5
BP 1 Serial Number 1
0 - 255
BP_1_SN1
0
BP 1 Serial Number 2
0 - 255
BP_1_SN2
0
BP 1 Serial Number 3
0 - 255
BP_1_SN3
0
BP 1 Serial Number 4
0 - 255
BP_1_SN4
0
BP 1 Serial Number 5
0 - 255
BP_1_SN5
0
BP1 Cntrl Angle Lo Limit
0-90
BP1_CALM
35
BP 2 Serial Number 1
0 - 255
BP_2_SN1
0
BP 2 Serial Number 2
0 - 255
BP_2_SN2
0
BP 2 Serial Number 3
0 - 255
BP_2_SN3
0
BP 2 Serial Number 4
0 - 255
BP_2_SN4
0
BP 2 Serial Number 5
0 - 255
BP_2_SN5
0
BP2 Cntrl Angle Lo Limit
0-90
BP2_CALM
35
COOL
Capacity Threshold Adjst
-10 - 10
Z_GAIN
1
Compressor Lockout Temp
-25 - 55
dF
OATLCOMP
40
Lead/Lag Operation ?
Yes/No
LLENABLE
No
Motor Master Control ?
Yes/No
MOTRMAST
No
Head Pressure Setpoint
80 - 150
dF
HPSP
113
Enable Compressor A1
Enable/Disable
CMPA1ENA
Enable
Enable Compressor A2
Enable/Disable
CMPA2ENA
Enable
Enable Compressor B1
Enable/Disable
CMPB1ENA
Enable
Enable Compressor B2
Enable/Disable
CMPB2ENA
Enable
CSB A1 Feedback Alarm
Enable/Disable
CSB_A1EN
Enable
CSB A2 Feedback Alarm
Enable/Disable
CSB_A2EN
Enable
CSB B1 Feedback Alarm
Enable/Disable
CSB_B1EN
Enable
CSB B2 Feedback Alarm
Enable/Disable
CSB_B2EN
Enable
CMPA1 Hi.Pr.Sw. Trip
365-415
PSIG
HPSATRIP
415
CMPB1 Hi.Pr.Sw. Trip
365-415
PSIG
HPSBTRIP
415
Hi SST Alert Delay Time
5 - 30
min
HSSTTIME
10
DEHU
Dehumidification Config
0-3
DHSELECT
0
Dehumidification Sensor
1-3
DHSENSOR
1
Econ disable in DH mode?
Yes/No
DHECONEN
No
Vent Reheat Setpt Select
0-1
DHVHTCFG
0
Vent Reheat RAT offset
0-8
^F
DHVRAOFF
0
Vent Reheat Setpoint
55-95
dF
DHVHT_SP
70
Dehumidify Cool Setpoint
40-55
dF
DHCOOLSP
45
Dehumidify RH Setpoint
10-90
%
DHRELHSP
55
DISP
Metric Display
Off/On
DISPUNIT
Off
Language Selection
0-1
LANGUAGE
0
Password Enable
Enable/Disable
PASS_EBL
Enable
Service Password
0000-9999
PASSWORD
1111
Contrast Adjustment
0-255
CNTR_ADJ
0
Brightness Adjustment
0-255
BRTS_ADJ
0
DLVT
Dmd Level Lo Heat On
-1 - 2
^F
DMDLHON
1.5
Dmd Level(+) Hi Heat On
0.5 - 20.0
^F
DMDHHON
0.5
Dmd Level(-) Lo Heat Off
0.5 - 2.0
^F
DMDLHOFF
1
Dmd Level Lo Cool On
-1 - 2
^F
DMDLCON
1.5
Dmd Level(+) Hi Cool On
0.5 - 20.0
^F
DMDHCON
0.5
Dmd Level(-) Lo Cool Off
0.5 - 2.0
^F
DMDLCOFF
1
Cool Trend Demand Level
0.1 - 5.0
^F
CTRENDLV
0.1
Heat Trend Demand Level
0.1 - 5.0
^F
HTRENDLV
0.1
Cool Trend Time
30 - 600
sec
CTRENDTM
120
Heat Trend Time
30 - 600
sec
HTRENDTM
120
DMDL
Demand Limit Select
0 - 3
DMD_CTRL
0
Demand Limit at 20 ma
0 - 100
%
DMT20MA
100
Loadshed Group Number
0 - 99
SHED_NUM
0
Loadshed Demand Delta
0 - 60
%
SHED_DEL
0
Maximum Loadshed Time
0 - 120
min
SHED_TIM
60
Demand Limit Sw.1 Setpt.
0 - 100
%
DLSWSP1
80
Demand Limit Sw.2 Setpt.
0 - 100
%
DLSWSP2
50
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...