![Carrier WEATHERMASTER 48Z030 Operation And Service Manual Download Page 9](http://html.mh-extra.com/html/carrier/weathermaster-48z030/weathermaster-48z030_operation-and-service-manual_2560339009.webp)
9
Table 4 — Fan Performance — 48ZG,ZN035 and 50ZG,ZN035 Units Without Discharge Plenum*
LEGEND
*If calculating static pressure for a 48 Series unit, be sure to add gas
heat pressure drop from Table 30A on page 32.
NOTES:
1. Fan performance is based on wet coils and clean 2-in. filters.
2. See Table 30A before using Fan Performance tables.
3. Conversion — Bhp to kW:
See Tables 26-28 for motor efficiency.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
7,000
246
0.84
301
1.19
352
1.58
398
2.01
440
2.46
479
2.93
514
3.40
547
3.90
8,000
266
1.14
315
1.50
362
1.92
406
2.37
447
2.85
484
3.35
519
3.87
552
4.39
10,000
310
1.98
350
2.36
389
2.80
427
3.30
464
3.83
499
4.38
532
4.96
564
5.55
12,000
357
3.20
390
3.60
424
4.06
457
4.58
489
5.15
520
5.74
551
6.36
580
7.01
14,000
406
4.87
435
5.28
463
5.76
492
6.30
520
6.89
548
7.52
576
8.18
603
8.86
15,000
430
5.89
458
6.31
485
6.80
511
7.35
538
7.95
564
8.59
590
9.26
616
9.96
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
7,000
577
4.40
606
4.91
633
5.43
659
5.95
684
6.49
707
7.03
730
7.58
752
8.14
8,000
583
4.94
612
5.49
640
6.05
666
6.62
691
7.19
715
7.78
738
8.37
760
8.97
10,000
594
6.16
623
6.79
651
7.42
677
8.07
703
8.73
727
9.39
751
10.06
774
10.74
12,000
609
7.67
636
8.36
663
9.05
689
9.77
714
10.49
738
11.22
762
11.97
785
12.72
14,000
629
9.57
655
10.30
680
11.04
704
11.81
728
12.59
751
13.38
774
14.18
796
14.99
15,000
641
10.69
666
11.44
690
12.20
714
12.99
737
13.79
760
14.61
782
15.44
804
16.28
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.4
3.6
3.8
4.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
7,000
773
8.70
793
9.27
813
9.85
832
10.43
8,000
782
9.57
802
10.18
823
10.80
842
11.43
10,000
796
11.42
817
12.11
838
12.81
858
13.52
12,000
807
13.48
828
14.25
849
15.02
869
15.80
14,000
818
15.82
840
16.66
860
17.50
880
18.35
15,000
825
17.13
846
18.00
866
18.87
886
19.76
48/50ZN units only.
Bhp —
Brake Horsepower
Kilowatts =
Bhp x .746
Motor efficiency
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...