![Carrier WEATHERMASTER 48Z030 Operation And Service Manual Download Page 122](http://html.mh-extra.com/html/carrier/weathermaster-48z030/weathermaster-48z030_operation-and-service-manual_2560339122.webp)
122
Table 95 — Thermistors and Unit Operation Control Pressure Transducers
LEGEND
FAN STATUS SWITCH — The units can be equipped with
an optional fan status switch that will monitor the pressure rise
across the indoor fans.
RETURN AIR CO
2
SENSOR — The unit can be equipped
with a return air IAQ CO
2
sensor that is used for the demand
control ventilation. The sensor is located in the return air sec-
tion and can be accessed from the filter access door.
BOARD ADDRESSES — Each board in the system has an
address. The MBB has a default address of 1 but it does have
an instance jumper that should be set to 1 as shown in Fig. 26.
For the other boards in the system there is a 4-dip switch head-
er on each board that should be set as shown below.
0 = On; 1 = Off
Accessory Control Components —
In addition to
the factory-installed options, the units can also be equipped
with several field-installed accessories that expand the control
features of the unit. The following hardware components can
be used as accessories.
ROOM THERMOSTATS — The
Comfort
Link™ controls
support a conventional electro-mechanical or electronic ther-
mostat that uses the Y1, Y2, W1, W2, and G signals. The
control also supports an additional input for an occupied/
unoccupied command that is available on some new thermo-
stats. The
Comfort
Link controls can be configured to run with
up to 6 stages of capacity. Although the unit can be configured
for normal 2-stage control, it is recommended that the multi-
stage control be used. The room thermostat is connected to
TB202.
The
Comfort
Link controls also support the use of space
temperature sensors and can be used with the T55 and T56
sensors. The controls can also be used with CCN communicat-
ing T58 room sensor. The T55 and T56 sensors are connected
to TB202 terminals 8, 9, and 10. The T58 sensor is connected
to the CCN connections on COMM board. Whenever a unit
equipped with heat is operated without a thermostat, the user
must install the red jumpers from R to W1, and W2 on TB202
for the heat function to work correctly.
SPACE CO
2
SENSORS — The
Comfort
Link controls also
support a CO
2
IAQ sensor that can be located in the space for
use in demand ventilation. The sensor must be a 4 to 20 mA
sensor and should be connected to TB202 terminals 11 and 12.
ECONOMIZER HUMIDITY CHANGEOVER SEN-
SORS — The
Comfort
Link controls support 5 different
changeover systems for the economizer. These are:
• Outdoor enthalpy switch
• Outdoor air dry bulb
• Differential dry bulb
• Outdoor air enthalpy curves
• Differential enthalpy
• Custom curves (a combination of an enthalpy/dewpoint
curve and a dry bulb curve).
The units are equipped as standard with an outdoor air
enthalpy control. Outside air and return air dry bulb sensors
which support the dry bulb changeover method are also
supplied as standard. If the other methods are to be used, then a
field-installed humidity sensor must be installed for outdoor air
enthalpy and customer curve control and two humidity sensors
must be installed for differential enthalpy. Installation holes are
pre-drilled and wire harnesses are installed in every unit for
connection of the humidity sensors. The
Comfort
Link controls
have the capability to convert the measured humidity and
dry bulb temperature into enthalpy.
SENSOR
DESCRIPTION AND LOCATION
PART NO.
Thermistors
CCT
Cooling Coil Thermistor input. Provided with factory-option hydronic heat. Located on face of the
hydronic heating coil. Consists of 4 thermistors wired into a 2x2 array.
HH79NZ039 (4)
LST
Limit Switch Thermistor. Provided with Staged Gas Control option. Located in the heating
compartment.
HH79NZ034
OAT
Outside Air Thermistor. Located in top of the return plenum, attached to roof pole.
HH79NZ039
RAT
Return Air Thermistor.
Without Economizer: Located on left side base rail in the return plenum.
With Economizer: Located on left side face of return damper section in the return plenum.
HH79NZ039
SAT
Supply Air Thermistor. Located in the Supply Fan section, on left side of the fan housing.
(May be relocated or replaced when unit is used with CCN Linkage systems; see page 60.)
HH79NZ039
LAT 1,2,3
Leaving Air Thermistors, provided with Staged Gas Control option. Shipped in the heating
compartment. Installer must pull out and mount in the supply duct.
HH79NZ034 (3)
Control Pressure Transducers
BP
Building Pressure. Provided with Modulating Power Exhaust, High-Capacity Power Exhaust
and Return Fan options. Located in the auxiliary control box (left-hand side of unit near return
plenum).
HK05ZG018
DPA
Discharge Pressure (refrigerant), Circuit A. Located on compressor A1 high-side connections.
HK05YZ007
DPB
Discharge Pressure (refrigerant), Circuit B. Located on compressor B1 high-side connections.
HK05YZ007
SPA
Suction Pressure (refrigerant), Circuit A. Located on compressor A1 low-side connections.
HK05YZ001
SPB
Suction Pressure (refrigerant), Circuit B. Located on compressor B1 low-side connections.
HK05YZ001
DSP
Duct Static Pressure. Provided with VAV models equipped with VFD or Inlet Guide Vane options.
Located in the auxiliary control box (right-hand side of unit near return plenum).
HK05ZG010
FT_SF
Supply Air Cfm (velocity pressure). Provided with factory-option return fan system
(sizes 075-105 only). Located in the supply fan compartment, on right side, on vertical post.
HK05ZG015
FT_RF
Return Air Cfm (velocity pressure). Provided with factory-option return fan system
(sizes 075-105 only). Located in auxiliary control box (right-hand side, filter access panel).
HK05ZG07
Outside Air CFM
Control
Outside Air Cfm Monitor (velocity pressure). Provided with the Outside Air Cfm Control option.
Located in auxiliary control box (right-hand side, filter access panel).
50ZZ400290 (030-070)
50ZZ400289 (075-105)
VAV —
Variable Air Volume
BOARD
SW1
SW2
SW3
SW4
RCB
0
0
0
0
ECB
1
0
0
0
SCB
0
0
0
0
CEM
0
0
0
0
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...