74
damper position will never exceed the bounds specified by
IAQ.M
and
EC.MN
during IAQ control.
If the building is occupied and the indoor fan is running and
the differential between IAQ and OAQ is less than
DAQ.L
, the
economizer will remain at
IAQ.M
. The economizer will not
close completely. The damper position will be 0 when the fan
is not running or the building is unoccupied. The damper posi-
tion may exceed
EC.MN
in order to provide free cooling.
The
Comfort
Link™ controls are configured for air quality
sensors which provide 4 mA at 0 ppm and 20 mA at 2000 ppm.
If a sensor has a different range, these bounds must be
reconfigured. These pertinent configurations for ranging the air
quality sensors are
IQ.R.L, IQ.R.H, OQ.R.L
and
OQ.R.H
. The
bounds represent the PPM corresponding to 4 mA (low) and
20 mA (high) for IAQ and OAQ, respectively.
If OAQ exceeds the OAQ Lockout Value (
OAQ.L
), then the
economizer will remain at
IAQ.M
. This is used to limit the use
of outside air which outdoor air CO
2
levels are above the
OAQ.L
limit. Normally a linear control of the damper vs. the
IAQ control signal can be used, but the control also supports
non-linear control. Different curves can be used based on the
Diff.IAQ Responsiveness Variable (
IAQ.R
)
. See Fig. 12.
SETTING UP THE SYSTEM — The IAQ configuration op-
tions are under the Local Display Mode
Configuration
→
IAQ
.
See Table 59.
IAQ Analog Sensor Config (
Configuration
→
IAQ
→
AQ.CF
→
IQ.A.C
) — This is used to configure the type of
IAQ position control. It has the following options:
•
IQ.A.C
= 0 (No analog input). If there is no other mini-
mum position control, the economizer minimum position
will be
Configuration
→
IAQ
→
EC.MN
and there will be
no IAQ control.
•
IQ.A.C
= 1 (IAQ analog input). An indoor air (space or
return air) CO
2
sensor is installed. If an outdoor air CO
2
sensor is also installed, or OAQ is broadcast on the CCN,
or if a default OAQ value is used, then the unit can per-
form IAQ control.
•
IQ.A.C
= 2 (IAQ analog input with minimum position
override) — If the differential between IAQ and OAQ
is above
Configuration
→
IAQ
→
AQ.SP
→
DAQ.H
, the
economizer minimum position will be the IAQ override
position (
Configuration
→
IAQ
→
AQ.SP
→
IQ.O.P
).
•
IQ.A.C
= 3 (4 to 20 mA minimum position) — With a 4
to 20 mA signal connected to TB202 terminal 11 and 12,
the economizer minimum position will be scaled linearly
from 0% (4 mA) to
EC.MN
(20 mA).
•
IQ.A.C
= 4 (10K potentiometer minimum position) — With
a 10K linear potentiometer connected to TB202 terminal 11
and 12, the economizer minimum position will be scaled
linearly from 0% (0 kilo-ohms) to
EC.MN
(10 kilo-ohms).
IAQ Analog Fan Config (
Configuration
→
IAQ
→
AQ.CF
→
IQ.A.F
) — This configuration is used to configure the control
of the indoor fan. If this option is used then the IAQ sensor
must be in the space and not in the return duct. It has the fol-
lowing configurations:
•
IQ.A.F
= 0 (No Fan Start) — IAQ demand will never
override normal indoor fan operation during occupied or
unoccupied period and turn it on.
•
IQ.A.F
= 1 (Fan On If Occupied) — IAQ demand will
override normal indoor fan operation and turn it on (if
off) only during the occupied period (CV operation with
automatic fan).
•
IQ.A.F
= 2 (Fan On Occupied/Unoccupied) — IAQ
demand will always override normal indoor fan operation
and turn it on (if off) during both the occupied and unoccu-
pied period. For
IQ.A.F
= 1 or 2, the fan will be turned on as
described above when DAQ is above the DAQ Fan On Set
Point (
Configuration
→
IAQ
→
AQ.SP
→
D.F.ON
). The fan
will be turned off when DAQ is below the DAQ Fan Off Set
Point (
Configuration
→
IAQ
→
AQ.SP
→
D.F.OF
). The con-
trol can also be set up to respond to a discrete IAQ input.
The discrete input is connected to TB204 terminal 11 and
12.
Table 59 — Indoor Air Quality Configuration
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
DCV.C
DCV ECONOMIZER SETPOINTS
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
IAQ.M
IAQ Demand Vent Min.Pos.
0 - 100
%
IAQMINP
0
O.C.MX
Economizer Min.Flow
0 - 20000
CFM
OACFMMAX
2000
O.C.MN
IAQ Demand Vent Min.Flow
0 - 20000
CFM
OACFMMIN
0
O.C.DB
Econ.Min.Flow Deadband
200 - 1000
CFM
OACFM_DB
400
AQ.CF
AIR QUALITY CONFIGS
IQ.A.C
IAQ Analog Sensor Config
0 - 4
IAQANCFG
0
IQ.A.F
IAQ 4-20 ma Fan Config
0 - 2
IAQANFAN
0
IQ.I.C
IAQ Discrete Input Config
0 - 2
IAQINCFG
0
IQ.I.F
IAQ Disc.In. Fan Config
0 - 2
IAQINFAN
0
OQ.A.C
OAQ 4-20ma Sensor Config
0 - 2
OAQANCFG
0
AQ.SP
AIR QUALITY SETPOINTS
IQ.O.P
IAQ Econo Override Pos.
0 - 100
%
IAQOVPOS
100
IQ.O.C
IAQ Override Flow
0 - 31000
CFM
IAQOVCFM
10000
DAQ.L
Diff.Air Quality LoLimit
0 - 1000
DAQ_LOW
100
DAQ.H
Diff. Air Quality HiLimit
100 - 2000
DAQ_HIGH
700
D.F.OF
DAQ PPM Fan Off Setpoint
0 - 2000
DAQFNOFF
200
D.F.ON
DAQ PPM Fan On Setpoint
0 - 2000
DAQFNON
400
IAQ.R
Diff. AQ Responsiveness
-5 - 5
IAQREACT
0
OAQ.L
OAQ Lockout Value
0 - 2000
OAQLOCK
0
OAQ.U
User Determined OAQ
0 - 5000
OAQ_USER
400
AQ.S.R
AIR QUALITY SENSOR RANGE
IQ.R.L
IAQ Low Reference
0 - 5000
IAQREFL
0
IQ.R.H
IAQ High Reference
0 - 5000
IAQREFH
2000
OQ.R.L
OAQ Low Reference
0 - 5000
OAQREFL
0
OQ.R.H
OAQ High Reference
0 - 5000
OAQREFH
2000
IAQ.P
IAQ PRE-OCCUPIED PURGE
IQ.PG
IAQ Purge
Yes/No
IAQPURGE
No
IQ.P.T
IAQ Purge Duration
5 - 60
min
IAQPTIME
15
IQ.P.L
IAQ Purge LoTemp Min Pos
0 - 100
%
IAQPLTMP
10
IQ.P.H
IAQ Purge HiTemp Min Pos
0 - 100
%
IAQPHTMP
35
IQ.L.O
IAQ Purge OAT Lockout
35 - 70
dF
IAQPNTLO
50
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...