143
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
ECONOMZR
Economizer Act.Curr.Pos.
%
ECONOPOS
Economizer 2 Act.Curr.Pos.
%
ECON2POS
Economizer Act.Cmd.Pos.
%
ECONOCMD
forcible
Economizer Active ?
ECACTIVE
Economizer Control Point
dF
ECONCPNT
Outside Air Temperature
dF
OAT
forcible
Evaporator Discharge Tmp
dF
EDT
Controlling Return Temp
dF
RETURN_T
forcible
Econo Current Min. Pos.
%
ECMINPOS
Econo Current Min. CFM
CFM
ECMINCFM
Outside Air CFM
CFM
OACFM
GENERAL
Occupied ?
YES/NO
OCCUPIED
forcible
Static Pressure
"H2O
SP
Building Pressure
"H2O
BP
Outside Air CFM
CFM
OACFM
Return Air CFM
CFM
RACFM
Supply Air CFM
CFM
SACFM
Outside Air Rel.Humidity
%
OARH
forcible
Return Air Rel.Humidity
%
RARH
forcible
Space Relative Humidity
%
SPRH
forcible
Space Temperature Offset
^F
SPTO
forcible
Supply Air Setpnt. Reset
^F
SASPRSET
forcible
Static Pressure Reset
SPRESET
forcible
IAQ - PPM Return CO2
IAQ
forcible
OAQ - PPM Return CO2
OAQ
forcible
IAQ Min.Pos.Override
%
IAQMINOV
forcible
GENERIC
20 points dependent upon
the configuration of the
"generics" table in the
Service-Config section on page 150
HEATING
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Heat Control Type……:
ascii text strings
Re-Heat Control Type...:
ascii text strings
Heating Mode………..:
ascii text strings
Requested Heat Stage
HT_STAGE
Ht.Coil Act.Current Pos.
%
HTCLRPOS
Heating Control Point
dF
HEATCPNT
Heat Relay 1
HS1
Heat Relay 2
HS2
Relay 3 W1 Gas Valve 2
HS3
Relay 4 W2 Gas Valve 2
HS4
Relay 5 W1 Gas Valve 3
HS5
Relay 6 W2 Gas Valve 3
HS6
Heat Interlock Relay
HIR
forcible
MODEDISP
System Mode…………:
ascii text strings
HVAC Mode…………..:
ascii text strings
Control Mode………..:
ascii text strings
Currently Occupied
On/Off
MODEOCCP
Timed Override in effect
On/Off
MODETOVR
DCV resetting min pos
On/Off
MODEADCV
Supply Air Reset
On/Off
MODESARS
Demand Limit in Effect
On/Off
MODEDMLT
Temp.Compensated Start
On/Off
MODETCST
IAQ pre-occ purge active
On/Off
MODEIQPG
Linkage Active - DAV
On/Off
MODELINK
Mech.Cooling Locked Out
On/Off
MODELOCK
HVAC Mode Numerical Form
number
MODEHVAC
MODETRIP
Unoccup. Cool Mode Start
UCCLSTRT
Unoccup. Cool Mode End
UCCL_END
Occupied Cool Mode Start
OCCLSTRT
Occupied Cool Mode End
OCCL_END
Ctl.Temp RAT,SPT or Zone
CTRLTEMP
Occupied Heat Mode End
OCHT_END
Occupied Heat Mode Start
OCHTSTRT
Unoccup. Heat Mode End
UCHT_END
Unoccup. Heat Mode Start
UCHTSTRT
HVAC Mode…………..:
ascii text strings
string
TEMPCTRL
Evaporator Discharge Tmp
dF
EDT
Leaving Air Temperature
dF
LAT
Mixed Air Temperature
dF
MAT
Controlling Return Temp
dF
RETURN_T
forcible
Controlling Space Temp
dF
SPACE_T
forcible
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...