Table 91 — Control Expansion Module (CEM) Inputs and Outputs
POINT
NAME
POINT DESCRIPTION
I/O
POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S)
PORT STATE
INPUTS
DHDISCIN
Dehumidify Switch Input
DI 1
J7, 1-2
2
0 = 24vac, 1= 0vac
DMD_SW1
Demand Limit Switch 1
DI 2
J7, 3-4
4
0 = 24vac, 1= 0vac
DMD_SW2
Demand Limit Switch 2
DI 3
J7, 5-6
6
0 = 24vac, 1= 0vac
PRES
Pressurization
DI 4
J7, 7-8
8
0 = 24vac, 1= 0vac
EVAC
Evacuation
DI 5
J7, 9-10
10
0 = 24vac, 1= 0vac
PURG
Smoke Purge
DI 6
J7, 11-12
12
0 = 24vac, 1= 0vac
IAQIN
IAQ - Discrete Input
DI 7
J7, 13-14
14
0 = 24vac, 1= 0vac
OACFM
Outside Air CFM
AN7
J6, 1-3
2 (1 = loop power)
(0-20mA input)
OARH
Outside Air Rel.Humidity
AN8
J6, 4-6
5 (4 = loop power)
(0-20mA input)
SPRH
Space Relative Humidity
AN9
J6, 7-9
8 (7 = loop power)
(0-20mA input)
RARH
Return Air Rel.Humidity
AN10
J6, 10-12
11 (10 = loop power)
(0-20mA input)
DMDLMTMA
4-20ma Demand Signal
AN1
J5, 1-2
1
(thermistor, ohms)
EDTRESMA
EDT Reset milliampere
AN2
J5, 3-4
3
(thermistor, ohms)
OAQ
OAQ - PPM Return CO2
AN3
J5, 5-6
5
(thermistor, ohms)
SPRESET
SP Reset milliamps
AN3
J5, 5-6
5
(thermistor, ohms)
AN4
J5, 7-8
7
(thermistor, ohms)
AN5
J5, 9-10
9
(thermistor, ohms)
AN6
J5, 11-12
11
(thermistor, ohms)
CEBD430351
TEST
1
CEPL130351-01
PWR
TEST 2
J1
J2
J4
J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS
DIP SWITCH (ALL ON)
Fig. 29 — Controls Expansion Board (CEM)
Summary of Contents for WEATHERMASTER 48Z030
Page 103: ...103 Fig 15 Typical Power Schematic Sizes 030 050 Shown a48 8408 ...
Page 104: ...104 Fig 16 Main Base Board Input Output Connections a48 8409 ...
Page 105: ...105 Fig 17 RCB ECB CEM SCB Input Output Connections a48 8410 ...
Page 106: ...106 Fig 18 Typical Gas Heat Unit Control Wiring 48Z055 105 Units Shown a48 8411 ...
Page 107: ...107 Fig 19 Typical Electric Heat Unit Control Wiring 50Z055 105 Units Shown a50 8248 ...
Page 108: ...108 Fig 20 Typical Power Wiring 115 V 48Z Units a48 8412 ...
Page 109: ...109 Fig 21 Typical Power Wiring 115 V 50Z Units a50 8249 ...
Page 110: ...110 Fig 22 Typical Gas Heat Section Size 055 105 Units Shown a48 8413 ...
Page 111: ...111 Fig 23 Component Arrangement Size 030 050 Units ...
Page 112: ...112 Fig 24 Component Arrangement Size 055 070 Units ...
Page 113: ...113 Fig 25 Component Arrangement Size 075 105 Units ...