29

8.7.2 - Reset

Reset means the active setpoint is modified so that less 
machine capacity is required. In the cooling mode the 

setpoint is increased, whereas in the heating mode it is 
decreased.
 
The reset can be based on the following possibilities:
• 

OAT that gives the measure of the load trends for the 
building.

• 

Return water temperature (

Δ

T provides the average 

building load).

 
The reset source and the reset parameters can be 

configured in the Main menu (RESETCFG – Reset 
Config). In response to a change in the reset source (e.g. 
OAT), the setpoint is normally reset to optimise unit 

performance.

The amount of reset is determined by linear interpolation 
based on the following parameters:

• 

A reference at which reset is zero (no reset value).

• 

A reference at which reset is maximum (full reset 
value).

• 

The maximum reset value.

Reset example in Cooling mode for the space temperature

Legend
A   Maximum reset value
B   Reference for zero reset
C   Reference for maximum reset
D   Building load

8.8 - Capacity limitation

Touch Pilot Junior allows for the constant control of the 
unit capacity by setting its maximum allowable capacity. 

Capacity limitation is expressed in percentage, where a 
limit value of 100% means that the unit may run with its 

full capacity (no limitation is implemented). 

The unit capacity can be limited:
• 

By means of user-controlled volt-free contacts. The 
unit capacity can never exceed the limit setpoint 
activated by these contacts.

• 

By lag limit [LAG_LIM] set by the master unit in the 

master/slave assembly

. If the unit is not in the Master/

Slave assembly, the lag limit value is equal to 100%.

• 

By night mode limitation control. The demand limit 
value in the night mode is selectable if the value is 
below the selected limit.

To set limit setpoints

1.  Navigate to the Main menu.

2. Select 

Setpoint

 (SETPOINT).

3. 

 Set 

Switch Limit Setpoint 1 / 2 / 3

 [lim_sp1 /2/ 3].

Switch Limit Setpoint 1 / 2 / 3 [lim_sp1 /2 / 3]

0 to 100%

100%

To verify lag limit set by the master unit

1.  Navigate to the Main menu.

2. Select 

General Parameters

 (GENUNIT).

3. Verify 

Lag Capacity Limit Value

 [LAG_LIM].

Lag Capacity Limit Value [LAG_LIM]

0 to 100%

100%

To set the night mode limit

1.  Navigate to the Configuration menu.

2. Select 

General Config 

(GENCONF).

3. Set 

Night Capacity Limit

 [nh_limit].

Night Capacity Limit [nh_limit]

0 to 100%

100%

Based on the limit source, the active demand limit value 

(DEM_LIM) is set to the lowest possible value. 

 

DEM_LIM can be forced by Network.

To verify active demand limit value

1.  Navigate to the Main menu.

2. Select 

General Parameters

 (GENUNIT).

3. Verify 

Active Demand Limit

 

Val

 [DEM_LIM].

Active Demand Limit Val [DEM_LIM]

0 to 100%

-

8.9 - Capacity control

The control adjusts the capacity to keep the water 
exchanger temperature at its setpoint. Compressors are 
started and stopped in a sequence designed to equalise the 
number of starts

 (value weighted by their operating time). 

8.9.1 - Circuit loading sequence

This function determines in which order the circuit 
capacity is changed. Compressor loading is managed by 
starting/stopping the compressors. Two types of 
sequencing, i.e. balanced and staged loading sequence, are 

available and can be configured by the user via the user 
interface (GENCONF – General Config).

Balanced loading sequence: 

The control maintains equal 

capacity between all circuits as the machine loads and 
unloads. Balanced loading sequence is the default 
sequence employed by the control.

Staged loading sequence:

 The control loads the lead circuit 

completely before the lag circuits are started. When the 

load is decreasing, the lag circuit is unloaded first. Staged 

loading sequence is active when one of the circuits is shut 
down due to its failure; the circuit is in capacity override 
mode; or the remaining circuits are shut down or fully 
charged.

 

 

20 

Reset based on OAT 

25 

Reset based on delta T 

Reset based on analog input 

20 

no_reset 

selection 

full_reset 

 

Summary of Contents for Touch Pilot Junior

Page 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Page 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Page 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Page 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Page 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Page 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Page 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Page 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Page 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Page 10: ...10 5 2 Touch Pilot Junior menu structure...

Page 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Page 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Page 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Page 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Page 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Page 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Page 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Page 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Page 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Page 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Page 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Page 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Page 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Page 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Page 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Page 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Page 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Page 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Page 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Page 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Page 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Page 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Page 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Page 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Page 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Page 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: