9.2 - Alarms description

9.2.1 - Alarms 

Name

Code

Description

Reset

Action taken

Possible cause

1

COOL_EWT_F

15001

Water Exchanger Entering Fluid 
Thermistor Failure

Automatic, if thermistor 
reading returns to normal

Unit shuts down

Defective thermistor 

2

COOL_LWT_F

15002

Water Exchanger Leaving Fluid Thermistor 
Failure

As above

As above

As above

3

DEFROST_T_A_F

15003

Circuit A Defrost Thermistor Failure

As above

Cooling mode: Unit 
continues to operate
Heating mode: Circuit A 
shuts down

As above

4

DEFROST_T_B_F

15004

Circuit B Defrost Thermistor Failure

As above

Cooling mode: Unit 
continues to operate
Heating mode: Circuit B 
shuts down

As above

5

OAT_F

15010

OAT Thermistor Failure

As above

Unit shuts down

As above

6

CHWSTEMP_F

15011

MASTER/Slave Common Fluid Thermistor 
Failure

As above

Master/Slave operation is 
disabled, each unit 
returns to the stand-
alone mode

As above

7

SUCTION_T_A_F

15012

Circuit A Suction Gas Thermistor Failure

As above

Circuit A shuts down

As above

8

SUCTION_T_B_F

15013

Circuit B Suction Gas Thermistor Failure

As above

Circuit B shuts down

As above

9

SGTC1_F

15044

Coil Suction Gas Thermistor Sensor 1 
Failure

As above

Circuit A shuts down (in 

heating mode);

None (in cooling mode)

As above

10

SGTC2_F

15045

Coil Suction Gas Thermistor Sensor 2 
Failure

As above

Circuit B shuts down (in 

heating mode);

None (in cooling mode)

As above

11

DP_A_F

12001

Circuit A Discharge Pressure Transducer 
Failure

Automatic, if sensor voltage 
reading returns to normal

Circuit A shuts down

Defective transducer

12

DP_B_F

12002

Circuit B Discharge Pressure Transducer 
Failure

As above

Circuit B shuts down

As above

13

SP_A_F

12004

Circuit A Suction Pressure Transducer 
Failure

As above

Circuit A shuts down

As above

14

SP_B_F

12005

Circuit B Suction Pressure Transducer 
Failure

As above

Circuit B shuts down

As above

15

SIOB_CIR_A_
COM_F

4901

Loss of communication with SIOB Board 
Number A

Automatic, if 
communication is 
re-established

Circuit A shuts down

As above

16

SIOB_CIR_B_
COM_F

4902

Loss of communication with SIOB Board 
Number B

As above

Circuit B shuts down

Bus installation fault, 
communication error

17

AUX1_COM_F

4601

Loss of communication with AUX1 Board

As above

Unit shuts down

As above

18

COOLER_
FREEZE_F

10001

Water Exchanger Freeze Protection

Automatic (the first alarm in 

the last 24 h) or Manual

Unit shuts down, the 
water exchanger pump is 
running

No water flow, 

defective thermistor

19

LOW_SUCTION_A_F 10005

Circuit A Low Saturated Suction 
Temperature

Automatic (the first alarm in 

the last 24 h) or Manual

Circuit A shuts down

Pressure transducer 
defective, EXV blocked or 
lack of refrigerant

20

LOW_SUCTION_B_F 10006

Circuit B Low Saturated Suction 
Temperature

As above

Circuit B shuts down 

As above

21

HIGH_SH_A_F

10008

Circuit A High Superheat

Manual

Circuit A shuts down

Pressure transducer 
defective, temperature 
sensor defective,  EXV 
blocked or lack of 
refrigerant

22

HIGH_SH_B_F

10009

Circuit B High Superheat

Manual

Circuit B shuts down

As above

23

LOW_SH_A_F

10011

Circuit A Low Superheat

Manual

Circuit A shuts down

As above

24

LOW_SH_B_F

10012

Circuit B Low Superheat

Manual

Circuit B shuts down

As above

25

COOLER_LOCK_F

10014

Interlock Failure

Automatic (if the unit was 
stopped) or Manual

Unit shuts down

Customer interlock input 
set on

26

CPA1_REVERSE_
ROT_F

10016

Compressor A1 Not Started Or Pressure 
Increase not Established

Manual

Compressor A1 shuts 
down

Compressor breaker or 
fuse fault,  compressor 
switch open

27

CPA2_REVERSE_
ROT_F

10017

Compressor A2 Not Started Or Pressure 
Increase not Established

Manual

Compressor A2 shuts 
down

As above

28

CPA3_REVERSE_
ROT_F

10018

Compressor A3 Not Started Or Pressure 
Increase not Established

Manual

Compressor A3 shuts 
down

As above

29

CPB1_REVERSE_
ROT_F

10020

Compressor B1 Not Started Or Pressure 
Increase not Established

Manual

Compressor B1 shuts 
down

As above

30

CPB2_REVERSE_
ROT_F

10021

Compressor B2 Not Started Or Pressure 
Increase not Established

Manual

Compressor B2 shuts 
down

As above

31

LOSS_COM_SM_F

10029

Loss of communication with System 
Manager

Automatic, if 
communication is 
re-established

Unit returns to the 
stand-alone mode

CCN bus installation 
defective

32

LOSS_COM_MS_F

10030

Master/Slave communication Failure

Automatic, if 
communication is 
re-established

Master/Slave operation is 
disabled, the unit returns 
to the stand-alone mode

CCN bus installation 
defective

Summary of Contents for Touch Pilot Junior

Page 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Page 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Page 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Page 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Page 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Page 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Page 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Page 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Page 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Page 10: ...10 5 2 Touch Pilot Junior menu structure...

Page 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Page 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Page 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Page 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Page 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Page 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Page 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Page 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Page 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Page 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Page 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Page 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Page 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Page 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Page 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Page 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Page 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Page 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Page 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Page 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Page 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Page 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Page 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Page 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Page 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Page 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: