24

8.1 - Unit start/stop control 

The unit state is determined based on a number of factors, 
including its operating type, active overrides, open 

contacts, master/slave configuration, or alarms triggered 

due to operating conditions.

The table given below summarizes the unit control type 
[ctrl_typ] and its running status with regard to the 
following parameters:

• 

Operating type:

 This operating type is selected using 

the 

Start/Stop

 button on the user interface.

LOFF

Local off

L-C

Local on

L-SC

Local schedule

Rem

Remote

Net

Network

Mast

Master unit

• 

Start/stop force command [CHIL_S_S]: 

Chiller start/

stop force command can be used to control the chiller 

state in the Network mode.

 

Command set to stop: 

The unit is halted. 

 

Command set to start: 

The unit runs in 

accordance with schedule 1.

• 

Remote start/stop contact status [Onoff_sw]:

 Start/

stop contact status can be used to control the chiller 
state in the Remote operating type.

• 

Master control type [ms_ctrl]: 

When the unit is the 

master unit in a two-chiller master/slave arrangement, 
the master unit may be set to be controlled locally, 
remotely or via network.

• 

Start/stop schedule [chil_occ]: 

Occupied or 

unoccupied status of the unit.

• 

Network emergency stop command [EMSTOP]: 

If 

activated, the unit shuts down regardless of the active 
operating type.

• 

General alarm: 

The unit shuts down due to failure.

Active operating type

Parameter status

Result

LOFF

L-C

L-SC

Rem

Net

Mast

Start/stop 
force 
command

Remote 
start/stop 
contact

Master 
control 
type

Start/stop  
time 
schedule

Network 
emergency 
shutdown

General 
alarm

Control 
type

Unit 
state

-

-

-

-

-

-

-

-

-

-

enable

-

-

off

-

-

-

-

-

-

-

-

-

-

-

yes

-

off

active

-

-

-

-

-

-

local

off

active

-

-

-

unoccupied

-

-

local

off

active

-

off

-

-

-

-

remote

off

active

-

-

-

unoccupied

-

-

remote

off

active

disable

-

-

-

-

-

network

off

active

-

-

-

unoccupied

-

-

network

off

active

-

-

local

unoccupied

-

-

local

off

active

-

off

remote

-

-

-

remote

off

active

-

-

remote

unoccupied

-

-

remote

off

active

disable

-

network

-

-

-

network

off

active

-

-

network

unoccupied

-

-

network

off

active

-

-

-

-

disable

no

local

on

active

-

-

-

occupied

disable

no

local

on

active

-

on_cool

-

occupied

disable

no

remote

on

active

-

on_heat

-

occupied

disable

no

remote

on

active

-

on_auto

-

occupied

disable

no

remote

on

active

enable

-

-

occupied

disable

no

network

on

active

-

-

local

occupied

disable

no

local

on

active

-

on_cool

remote

occupied

disable

no

remote

on

active

-

on_heat

remote

occupied

disable

no

remote

on

active

-

on_auto

remote

occupied

disable

no

remote

on

active

enable

-

network

occupied

disable

no

network

on

IMPORTANT: When the unit is stopping or there is a 
demand to stop the unit, compressors are stopped 
consecutively. 

8 - STANDARD CONTROL OPERATIONS AND OPTIONS

In case of emergency stop, all compressors are stopped at 
the same time.

Summary of Contents for Touch Pilot Junior

Page 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Page 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Page 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Page 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Page 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Page 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Page 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Page 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Page 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Page 10: ...10 5 2 Touch Pilot Junior menu structure...

Page 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Page 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Page 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Page 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Page 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Page 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Page 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Page 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Page 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Page 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Page 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Page 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Page 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Page 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Page 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Page 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Page 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Page 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Page 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Page 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Page 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Page 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Page 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Page 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Page 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Page 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...