background image

31

8.12 - Coil pressure control

The coil pressure of each circuit is managed by a maximum 
of two fans in circuit A and one fan in circuit B. 

30RBS/30RQS units are fitted with fixed speed fans or 

variable speed fans which provide higher part load 

efficiency and reduced acoustic levels

In cooling mode, the condensing pressure is controlled 

independently in each circuit based on the saturated 
condensing temperature. The control permanently adjusts 
its setpoint to guarantee optimal performance and ensure 
anti-short-cycle protection of the fans.

In heating mode, the evaporating pressure is controlled 

independently on each circuit based on the saturated 
suction temperature. The control permanently adjusts its 
setpoint to guarantee optimal performance, delay and limit 
frost accumulation on coils.

8.13 - Holidays

This function is used to define 16 holiday periods. Each 
period is defined by three parameters, 

i.e. the month, the 

start day and the duration of the holiday period. 

During the holiday periods the controller will be in 
occupied or unoccupied mode, depending on the periods 

validated as holidays. Each holiday period can be modified 
by the user via the Configuration menu (HOLIDAY – 
Holiday Menu).

To modify holiday periods

1.  Navigate to the Configuration menu.

2. Select 

Holiday Menu

 (HOLIDAY).

3.  Choose the holiday period, e.g. HOLDY_01.

4. Set 

Holiday Start Month

 [HOL_MON], 

 

Start Day

 [HOL_DAY], 

 

Duration (days)

 [HOL_LEN].

Holiday Start Month [HOL_MON]

0-12

0

Start Day [HOL_DAY]

0-31

0

Duration (days) [HOL_LEN]

0-99

0

8.14 - BACnet option

The BACnet/IP communication protocol is used by BMS 

or the programmable controllers to communicate with the 
control.

IMPORTANT: BACnet option can be installed only by 
Carrier service.

8.15 - Desuperheater option

30RBS/30RQS

 units may be fitted with a desuperheater 

that allows for better energy management. 

The desuperheater is used to extract the high pressure, 
high temperature heat from the refrigerant to 
“desuperheat” it to a lower pressure refrigerant. The 
vapour that goes into the desuperheater is not fully 
condensed; therefore, the refrigerant vapour must be 
channelled to a separate heat exchanger where the 
condensing process occurs.

To set minimal condensing setpoint

1.  Navigate to the Main menu.

2. Select 

Setpoint

 (SETPOINT).

3. Set 

Desuperheat Min SCT

 [min_sct].

Desuperheat Min SCT [min_sct]

26.7 to 60.0°C 

40.0°C 

80.0 to 140.0°F

104.0°F

8.16 - Defrost cycle for heat pumps

When the outside air temperature is low and the ambient 
humidity is high, the probability of frost forming on the 
surface of the outdoor coil increases. The frost covering the 

outdoor coil may decrease the air flow across the coil and 

lead to lower performance of the unit. To remove the frost 
from the coil, the control initiates the defrost cycle when 
necessary. 

During the defrost cycle, the circuit is forced into the 
cooling mode. To prevent the water loop from cooling 
down, optional electric heating may be started. The defrost 
cycle lasts until the end of defrost temperature is achieved.

8.17 - Master/Slave assembly

The control system allows for master/slave control of two 

units linked by the CCN network. The master unit can be 

controlled locally, remotely or by network commands 

(CCN), while the slave unit remains in Network mode. 

All control commands to the master/slave assembly  

(start/stop, setpoint selection, heating/cooling, etc.) are 
handled by the unit which is configured as the master. The 

commands are transmitted automatically to the slave unit.

If the master chiller is turned off while the master/slave 

function is active, then the slave chiller will be stopped.
Under certain circumstances, the slave unit may be started 

first to ensure that the run times of the two units are 

equalised.

In the event of a communication failure between the two 

units, each unit will return to an autonomous operating 

mode until the fault is cleared. If the master unit is stopped 

due to an alarm, the slave unit is authorised to start.

IMPORTANT: Master/slave assembly can be configured 

only by Carrier service.

Summary of Contents for Touch Pilot Junior

Page 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Page 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Page 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Page 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Page 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Page 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Page 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Page 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Page 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Page 10: ...10 5 2 Touch Pilot Junior menu structure...

Page 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Page 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Page 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Page 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Page 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Page 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Page 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Page 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Page 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Page 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Page 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Page 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Page 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Page 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Page 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Page 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Page 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Page 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Page 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Page 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Page 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Page 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Page 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Page 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Page 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Page 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...

Reviews: