20
Setpoint Menu – SETPOINT
Point name
Status
Default
Unit
Displayed text*
Description
1
csp1
-28.9 to 20.0
-20.0 to 68.0
7.0
44.6
°C
°F
Cooling Setpoint 1
Cooling setpoint 1
2
csp2
-28.9 to 20.0
-20.0 to 68.0
7.0
44.6
°C
°F
Cooling Setpoint 2
Cooling setpoint 2
3
hsp1
25.0 to 55.0
77.0 to 131.0
38.0
100.4
°C
°F
Heating Setpoint 1
Heating setpoint 1
4
hsp2
25.0 to 55.0
77.0 to 131.0
38.0
100.4
°C
°F
Heating Setpoint 2
Heating setpoint 2
5
ramp_sp
0.1 to 1.1
0.2 to 2.0
0.6
1.0
^C
^F
Ramp Loading
Ramp loading
6
cauto_sp
3.9 to 50.0
39.0 to 122.0
23.9
75.0
°C
°F
Cool Changeover Setpt
Cool changeover setpoint
7
hauto_sp
0 to 46.1
32.0 to 115.0
17.8
64.0
°C
°F
Heat Changeover Setpt
Heat changeover setpoint
8
lim_sp1
0 to 100
100
%
Switch Limit Setpoint 1
Switch limit setpoint 1
9
lim_sp2
0 to 100
100
%
Switch Limit Setpoint 2
Switch limit setpoint 2
10
lim_sp3
0 to 100
100
%
Switch Limit Setpoint 3
Switch limit setpoint 3
11
min_sct
26.7 to 60.0
80.0 to 140.0
40.0
104.0
°C
°F
Desuperheater Min Sct
Desuperheater minimum saturated condensing
temperature
*Depends on the selected language (English by default).
7.2 - Configuration menu
(CONFIG)
Icon
Displayed text*
Description
Name
General Config
General configuration
GENCONF
Pump Configuration
Pump configuration
PUMPCONF
Heat/Cool Config
Heat/Cool configuration
HCCONFIG
Reset Config
Reset configuration
RESETCFG
User Configuration
User configuration
USERCONF
Schedule
Schedule menu
SCHEDULE
Holiday
Holiday menu
HOLIDAY
Broadcast
Broadcast menu
BROADCAST
Date/Time
Date/time configuration
DATETIME
Control Identification Control identification
CTRL_ID
*Depends on the selected language (English by default).
CAUTION
Since specific units may not include
additional features,
some tables may contain parameters that cannot be