11
The bell located in the upper-right part of the screen lights
when any fault is detected.
By default, the parameters are presented in metric units.
For more information on how to change the system of
measurement, see section 5.8.3.
5.5 - Start the unit
With the unit in the Local off mode, press the
Start/Stop
button
to display the list of operating modes and
select the required mode.
Local On
Local On: The unit is in the local control mode and allowed to
start.
Local
Schedule
Local Schedule: The unit is in the local control mode and
allowed to start if the period is occupied.
Network
Network: The unit is controlled by network commands and
allowed to start if the period is occupied.
Remote
Remote: The unit is controlled by external commands and
allowed to start if the period is occupied.
Master
Master: The unit operates as the master in the master/slave
assembly and allowed to start if the period is occupied.
IMPORTANT: When entering the menu, please note that
the currently selected item corresponds to the last running
operating mode.
5.6 - Stop the unit
To stop the unit, press the
Start/Stop
button
Confirm the unit shutdown by pressing
Confirm Stop
or
cancel the unit shutdown by pressing the
Back
button
5.3 - Read the welcome screen
The Welcome screen is the first screen shown after starting
the user interface. It displays the application name as well
as the current software version number.
Home button
Software version number
To exit the Welcome screen, press
Information message box
The information box displayed in the status bar at the
bottom of the screen includes relevant messages regarding
the current user action.
All screens presented further in this manual may display
the following messages:
MESSAGE
STATUS
COMMUNICATION FAILURE!
Equipment controller did not respond while
reading the table content.
ACCESS DENIED!
Equipment controller denies access to one of
the tables.
LIMIT EXCEEDED!
The value entered exceeds the parameter limit.
Save changes?
Modifications have been made. The exit must be
confirmed by pressing Save or Cancel.
HIGHER FORCE IN EFFECT!
Equipment controller rejects Force or Auto
command.
5.4 - Explore the synoptic screen
The Synoptic screen provides an overview of the system
control, allowing the user to monitor the vapour-refrigeration
cycle.
The diagram indicates the current status of the unit, giving
information on the unit capacity, the status of water heat
exchanger pumps, and the pre-defined setpoint parameter.
All unit functions can be accessed by pressing the
Main
menu
button
IMPORTANT: The synoptic screen display may vary
depending on pumps configuration.
1
4
3
2
5
1
Outdoor air temperature
2
Unit capacity percentage
3 Setpoint
4
Evaporator inlet and outlet water temperature
5
Status screen message
Shows the last
mode selected