17
Temperature Menu – TEMP
Point name
Status
Unit
Displayed text*
Description
1
EWT
-
°C / °F
Entering Water Temp
Entering water temperature: Used for capacity control
2
LWT
-
°C / °F
Leaving Water Temp
Leaving water temperature: Used for capacity control
3
OAT
-
°C / °F
External Temperature
Outdoor air temperature: Used to determine a number of control
mechanisms such as heat/cool changeover, water exchanger
heater operation, defrost cycle
4
CHWSTEMP
-
°C / °F
Common Master/Slave Temp
Common master/slave temperature
5
SCT_A
-
°C / °F
Saturated Cond Tmp A
Saturated condensing temperature, circuit A
6
SST_A
-
°C / °F
Saturated Suction Tmp A
Saturated suction temperature, circuit A
7
SCT_B
-
°C / °F
Saturated Cond Tmp B
Saturated condensing temperature, circuit B
8
SST_B
-
°C / °F
Saturated Suction Tmp B
Saturated suction temperature, circuit B
9
DEFRT_A
-
°C / °F
Defrost Temp Cir A
Defrost temperature, circuit A (heat pumps only)
10
DEFRT_2
-
°C / °F
Defrost Temp Second Coil
Defrost temperature on the second coil on circuit A (heat pumps
only)
11
sgtc1
-
°C / °F
Suction Gas Temp Coil 1
Suction gas temperature coil 1
12
sgtc2
-
°C / °F
Suction Gas Temp Coil 2
Suction gas temperature coil 2
*Depends on the selected language (English by default).
Pressure Menu – PRESSURE
Point name
Status
Unit
Displayed text*
Description
1
DP_A
-
kPa / PSI
Discharge Pressure A
Compressor discharge pressure, circuit A
2
SP_A
-
kPa / PSI
Suction Pressure A
Compressor suction pressure, circuit A
3
DP_B
-
kPa / PSI
Discharge Pressure B
Compressor discharge pressure, circuit B
4
SP_B
-
kPa / PSI
Suction Pressure B
Compressor suction pressure, circuit B
*Depends on the selected language (English by default).
Inputs
Menu
– INPUTS
Point name
Status
Unit
Displayed text*
Description
1
ONOFF_SW
open/close
-
Remote On/Off Switch
Remote On/Off switch
2
HC_SW
open/close
-
Remote Heat/Cool Switch
Remote Heat/Cool switch
3
on_ctrl
xxx
-
Current Control
Current control status: Off, On Cool, On Heat, On Auto
4
SETP_SW
open/close
-
Remote Setpoint Switch
Remote setpoint switch
5
LIM_SW1
open/close
-
Limit Switch 1
Demand limit switch 1
6
LIM_SW2
open/close
-
Limit Switch 2
Demand limit switch 2
7
LIM_ANAL
-
mA
Limit Analog Input
Limit Analog Input 4-20mA
8
FLOW_SW
open/close
-
Flow Switch
Water exchanger flow switch
9
leak_v
-
V
Leakage detector #1 val
Leakage detector 1
10
leak_2_v
-
V
Leakage detector #2 val
Leakage detector 2
11
DSHT_SW
open/close
-
Desuperheater Switch
Desuperheater switch
12
PWRIN_ST
open/close
-
Power Input Stable
Power input stable
13
HP_SWA
open/close
-
HP Switch Circuit A
High pressure switch, circuit A
14
HP_SWA3B
open/close
-
HP Switch Circuit A3/B
High pressure switch, circuit B
15
bacdongl
no/yes
-
BACnet Dongle
BACnet dongle status (BACnet option)
*Depends on the selected language (English by default).