   Runtime Menu – RUNTIME 

Point name

Status

Unit

Displayed text*

Description

1

hr_mach

-

hour

Machine Operating Hours

Unit operating hours

2

st_mach

-

-

Machine Starts Number

Number of unit starts

3

hr_cp_a1

-

hour

Compressor A1 Hours

Operating hours, compressor A1

4

st_cp_a1

-

-

Compressor A1 Starts

Number of starts, compressor A1

5

hr_cp_a2

-

hour

Compressor A2 Hours

Operating hours, compressor A2

6

st_cp_a2

-

-

Compressor A2 Starts

Number of starts, compressor A2

7

hr_cp_a3

-

hour

Compressor A3 Hours

Operating hours, compressor A3

8

st_cp_a3

-

-

Compressor A3 Starts

Number of starts, compressor A3

9

hr_cp_b1

-

hour

Compressor B1 Hours

Operating hours, compressor B1

10

st_cp_b1

-

-

Compressor B1 Starts

Number of starts, compressor B1

11

hr_cp_b2

-

hour

Compressor B2 Hours

Operating hours, compressor B2

12

st_cp_b2

-

-

Compressor B2 Starts

Number of starts, compressor B2

13

hr_cpum1

-

hour

Water Pump #1 Hours

Operating hours, water pump 1

14

hr_cpum2

-

hour

Water Pump #2 Hours

Operating hours, water pump 2

15

hr_fana1

-

hour

Circuit A Fan #1 Hours

Operating hours, fan 1, circuit A

16

st_fana1

-

-

Circuit A Fan #1 Starts

Number of starts, fan 1, circuit A

17

hr_fana2

-

hour

Circuit A Fan #2 Hours

Operating hours, fan 2, circuit A

18

st_fana2

-

-

Circuit A Fan #2 Starts

Number of starts, fan 2, circuit A

19

hr_fanb1

-

hour

Circuit B Fan #1 Hours

Operating hours, fan 1, circuit B

20

st_fanb1

-

-

Circuit B Fan #1 Starts

Number of starts, fan 1, circuit B

21

nb_def_a

-

-

Circuit A Defrost Number

Defrost session number, circuit A

22

nb_def_b

-

-

Circuit B Defrost Number

Defrost session number, circuit B

*Depends on the selected language (English by default).

  DC Free Cooling Status Menu – FCOOL_ST

Point name

Status

Unit

Displayed text*

Description

1

fc_oat

0 to 0

°C / °F

Free Cooling OAT

Free Cooling OAT (see section 8.10)

2

fc_lwt

0 to 0

°C / °F

FC Leaving Water Temp

Free Cooling LWT

3

fc_wloop

0 to 0

°C / °F

FC Water Loop Temp

Free Cooling water loop temperature

4

m_fcool

no/yes

-

Free Cooling Mode Active

Free Cooling mode – status

5

fc_cap

0 to 100

%

FC Capacity

Capacity in Free Cooling mode

6

fc_fanst

0 to 7

-

FC Fan Stage

Number of fan stages in Free Cooling

7

FC_HOUR

0 to 999999

hour

FC Operating Hours

Free Cooling running time

8

FC_FAN1S

0 to 999999

-

FC Fan Stage 1 Start

Number of starts, FC fan stage 1

9

FC_FAN1H

0 to 999999

-

FC Fan Stage 1 Hours

Operating hours, FC fan stage 1

10

FC_FAN2S

0 to 999999

-

FC Fan Stage 2 Start

Number of starts, FC fan stage 2

11

FC_FAN2H

0 to 999999

-

FC Fan Stage 2 Hours

Operating hours, FC fan stage 2

12

FC_FAN3S

0 to 999999

-

FC Fan Stage 3 Start

Number of starts, FC fan stage 3

13

FC_FAN3H

0 to 999999

-

FC Fan Stage 3 Hours

Operating hours, FC fan stage 3

14

FC_FAN4S

0 to 999999

-

FC Fan Stage 4 Start

Number of starts, FC fan stage 4

15

FC_FAN4H

0 to 999999

-

FC Fan Stage 4 Hours

Operating hours, FC fan stage 4

16

FC_FAN5S

0 to 999999

-

FC Fan Stage 5 Start

Number of starts, FC fan stage 5

17

FC_FAN5H

0 to 999999

-

FC Fan Stage 5 Hours

Operating hours, FC fan stage 5

18

FC_FAN6S

0 to 999999

-

FC Fan Stage 6 Start

Number of starts, FC fan stage 6

19

FC_FAN6H

0 to 999999

-

FC Fan Stage 6 Hours

Operating hours, FC fan stage 6

20

FC_FAN7S

0 to 999999

-

FC Fan Stage 7 Start

Number of starts, FC fan stage 7

21

FC_FAN7H

0 to 999999

-

FC Fan Stage 7 Hours

Operating hours, FC fan stage 7

*Depends on the selected language (English by default).

  Modes Menu – MODES

Point name

Status

Unit

Displayed text*

Description

1

m_delay

no/yes

-

Delay Active

Delay active (when switching between modes)

2

m_2ndspt

no/yes

-

Second Setpoint Active

Second setpoint active (during unoccupied periods)

3

m_reset

no/yes

-

Reset Active

Reset is active

4

m_limit

no/yes

-

Demand Limit Active

Demand limit active

5

m_ramp

no/yes

-

Ramp Loading Active

Ramp loading active

6

m_cooler

no/yes

-

Cooler Heater Active

Water exchanger heater active

7

m_pmprot

no/yes

-

Pump Rot Active

Pump rotation active

8

m_pmpper

no/yes

-

Pump Per Active

Periodical pump start active 

9

m_night

no/yes

-

Night Low Noise Active

Night low noise mode active

10

m_SM

no/yes

-

System Manager Active

System Manager active

11

m_leadla

no/yes

-

Master Slave Active

Master/Slave active

12

m_auto

no/yes

-

Auto Changeover Active

Auto changeover active

13

m_heater

no/yes

-

Electric Heat Active

Electric heating active

14

m_lo_ewt

no/yes

-

Heating Low EWT Lockout

Heating low EWT lockout

15

m_boiler

no/yes

-

Boiler Active

Boiler active

16

m_ice

no/yes

-

Ice Mode Active

Ice mode active

17

m_defr_a

no/yes

-

Defrost Active On Cir A

Defrost active, circuit A

18

m_defr_b

no/yes

-

Defrost Active On Cir B

Defrost active, circuit B

19

m_sst_a

no/yes

-

Low Suction Circuit A

Low suction temperature, circuit A

20

m_sst_b

no/yes

-

Low Suction Circuit B

Low suction temperature, circuit B

21

m_dgt_a

no/yes

-

High DGT Circuit A

High discharge gas temperature, circuit A

22

m_dgt_b

no/yes

-

High DGT Circuit B

High discharge gas temperature, circuit B

23

m_hp_a

no/yes

-

High Pres Override Cir A

High pressure override, circuit A

24

m_hp_b

no/yes

-

High Pres Override Cir B

High pressure override, circuit B

25

m_sh_a

no/yes

-

Low SuperHeat Circuit A

Low superheat, circuit A

26

m_sh_b

no/yes

-

Low SuperHeat Circuit B

Low superheat, circuit B

*Depends on the selected language (English by default).

Summary of Contents for Touch Pilot Junior

Page 1: ...CONTROLS MANUAL Touch Pilot Junior 30RBS 39 160 30RQS 39 160 Original document...

Page 2: ...1 5 6 Stop the unit 11 5 7 Set the schedule 12 5 8 Manage display settings 12 5 9 Monitor unit parameters 13 5 10 Modify unit parameters 14 5 11 Override system configuration 14 6 WEB CONNECTION 15 6...

Page 3: ...ation and forms no part of any offer for sale or any sale contract The manufacturer reserves the right to change the design at any time without notice 9 DIAGNOSTICS 32 9 1 Control diagnostics 32 9 2 A...

Page 4: ...the language of the system all labels will be in the language selected by the user Please read all instructions prior to proceeding with any work Pay attention to all safety warnings The information p...

Page 5: ...box covers and motor frames with great care 2 CONTROL OVERVIEW 2 1 Control system Carrier 30RBS chillers and 30RQS heat pumps come with a Touch Pilot Junior control that serves as the user interface a...

Page 6: ...mpressor technology X X Water exchanger heater X X Defrost mechanism X Diagnostics X X Variable speed fans O O High static fan O O Fixed or variable speed pumps O O Cooling control X X Heating control...

Page 7: ...reenLEDflashescontinuouslyonallboardstoshow thattheboardiscommunicatingcorrectlyoveritsinternal bus LENbus IfthegreenLEDisnotflashing this indicatesaLENbuswiringproblemoraconfigurationissue 4 HARDWARE...

Page 8: ...erating mode is selected based on OAT 4 8 2 Volt free setpoint selection contact This dry contact input is used to switch between setpoints It is active only when the control is in Remote mode Cooling...

Page 9: ...rent unit operating status etc Resistive touch screen technology Web connectivity Custom language support 5 1 Touch Pilot Junior overview Touch Pilot Junior provides access to the following screens We...

Page 10: ...10 5 2 Touch Pilot Junior menu structure...

Page 11: ...r starting the user interface It displays the application name as well as the current software version number Home button Software version number To exit the Welcome screen press Information message b...

Page 12: ...f the controller change the system of measurement imperial or metric and enter a password to gain access to more control options To access the User Login screen press the Log button in the upper right...

Page 13: ...t Junior allows users to add new languages to the control To learn more about language customization please contact your local Carrier representative 5 8 3 System of measurement The control offers the...

Page 14: ...rd protected see also section 5 8 1 Press the field corresponding to the parameter to be modified and introduce all the necessary changes Press the Up Down buttons to navigate between the screens Once...

Page 15: ...6 WEB CONNECTION 6 1 Web interface The Touch Pilot Junior control can be accessed via a web browser Internet Explorer Mozilla Firefox etc Connection is from a PC using a web browser with Java CAUTION...

Page 16: ...OOL Heat Cool status Heating Cooling status 6 HC_SEL 0 to 2 Heat Cool Select Heating Cooling selection 0 Cool 1 Heat 2 Auto 0 Cool 1 Heat 2 Auto 7 SP_SEL 0 to 2 Setpoint Select Setpoint select 0 Auto...

Page 17: ...ion 1 DP_A kPa PSI Discharge Pressure A Compressor discharge pressure circuit A 2 SP_A kPa PSI Suction Pressure A Compressor suction pressure circuit A 3 DP_B kPa PSI Discharge Pressure B Compressor d...

Page 18: ...pumps 20 C_HEATER off on Cooler Drain Pan Heatr Water exchanger Drain pan heater 21 BOILER off on Boiler Command Boiler status 22 EHS_STEP Electrical Heat Stage Electric heating stages 23 ALARM_R off...

Page 19: ...2 FC_FAN3S 0 to 999999 FC Fan Stage 3 Start Number of starts FC fan stage 3 13 FC_FAN3H 0 to 999999 FC Fan Stage 3 Hours Operating hours FC fan stage 3 14 FC_FAN4S 0 to 999999 FC Fan Stage 4 Start Num...

Page 20: ...itch Limit Setpoint 2 Switch limit setpoint 2 10 lim_sp3 0 to 100 100 Switch Limit Setpoint 3 Switch limit setpoint 3 11 min_sct 26 7 to 60 0 80 0 to 140 0 40 0 104 0 C F Desuperheater Min Sct Desuper...

Page 21: ...ked if Pump Off Water flow is checked when the pump is off Depends on the selected language English by default Heat Cool Config Menu HCCONFIG Point name Status Default Unit Displayed text Description...

Page 22: ...Depends on the selected language English by default Schedule Menu SCHEDULE Point name Status Default Unit Displayed text Description 1 OCCPC01S OCCPC01S Schedule Menu Unit on off time schedule 2 OCCPC...

Page 23: ...s Daylight sav time on Daylight saving time on off 8 no yes Today is a holiday The present day is a holiday 9 tom_hol no yes Tomorrow is a holiday The following day is a holiday Depends on the selecte...

Page 24: ...the unit shuts down regardless of the active operating type General alarm The unit shuts down due to failure Active operating type Parameter status Result LOFF L C L SC Rem Net Mast Start stop force...

Page 25: ...ling or heating is determined based on the following parameters Control type Local Remote or Network Local heat cool selection hc_sel Heat Cool selection when the unit is running in Local mode Control...

Page 26: ...when mechanical heating is insufficient 8 4 1 Boiler control Boiler is activated when the outside air temperature is below the user configured boiler outdoor temperature threshold which is by default...

Page 27: ...guration PUMPCONF 3 Set Pump Rotation Delay pump_del Pump Rotation Delay pump_del 24 to 3000h 48h 8 5 4 Customer pumps configuration Units fitted with external pumps may have only fixed speed pumps av...

Page 28: ...represents the water temperature that the unit must produce The required capacity can be decreased depending on the unit load operating conditions Control point Active setpoint Reset The control poin...

Page 29: ...etpoint 1 2 3 lim_sp1 2 3 Switch Limit Setpoint 1 2 3 lim_sp1 2 3 0 to 100 100 To verify lag limit set by the master unit 1 Navigate to the Main menu 2 Select General Parameters GENUNIT 3 Verify Lag C...

Page 30: ...ve when the outdoor air temperature is below 0 C 32 F Starting free cooling The free cooling mode is ENABLED when the free cooling OAT fc_oat is below the water loop temperature and the start threshol...

Page 31: ...heat from the refrigerant to desuperheat it to a lower pressure refrigerant The vapour that goes into the desuperheater is not fully condensed therefore the refrigerant vapour must be channelled to a...

Page 32: ...the unit is still running The highlighted bell icon indicates that the unit is shut down due to a detected fault 9 1 1 Current alarms All currently active alarms can be found in the Current Alarms me...

Page 33: ...tion fault communication error 17 AUX1_COM_F 4601 Loss of communication with AUX1 Board As above Unit shuts down As above 18 COOLER_ FREEZE_F 10001 Water Exchanger Freeze Protection Automatic the firs...

Page 34: ...ectrical issue 50 SIOB_LOW_VOLT_ CIRB_F 57002 Circuit B SIOB Low Voltage Failure As above Unit shuts down As above 51 WP_IN_F 12024 Water Exchanger Entering Fluid Transducer Failure Automatic if senso...

Page 35: ...arm CPU fault Contact Carrier Service 24 Alarm Communication error trip Contact Carrier Service 26 Alarm Current detector fault Contact Carrier Service 27 Alarm Optional circuit board type error Conta...

Page 36: ...No 10099 02 2016 Supersedes order No 10099 08 2015 Manufacturer Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European...