21
General Config Menu – GENCONF
Point name
Status
Default
Unit
Displayed text*
Description
1
lead_cir
0 to 2
0
-
Cir Priority Sequence
Circuit priority sequence
0=Auto 1=A Lead 2=B Lead
0 = Automatic changeover
1 = Circuit A lead
2 = Circuit B lead
2
seq_typ
no/yes
no
-
Staged Loading Sequence
Staged loading sequence
3
ramp_sel
no/yes
no
-
Ramp Loading Select
Ramp loading sequence
4
off_on_d
1 to 15
1
min
Unit Off to On Delay
Unit OFF to ON delay
5
nh_limit
0 to 100
100
%
Night Capacity Limit
Night capacity limitation
6
nh_start
00:00
00:00
-
Night Mode Start Hour
Night mode start hour
7
nh_end
00:00
00:00
-
Night Mode End Hour
Night mode end hour
8
bas_menu
0 to 3
0
-
Basic Menu Config
Basic menu configuration
0 = All Access
0 = All access
1 = no alarm menu
1 = Alarm menu
2 = no setpoint menu
2 = Setpoint menu unavailable
3 = 1 + 2
3 = Alarm and Setpoint menus are unavailable
*Depends on the selected language (English by default).
Pump Configuration Menu – PUMPCONF
Point name
Status
Default
Unit
Displayed text*
Description
1
pump_seq
0 to 4
0
-
Water Pumps Sequence
Water pumps sequence
0 = No Pump
0 = No pump
1 = One Pump Only
1 = One pump only (units with one pump)
2 = Two Pumps Auto
2 = Two pumps automatic control
3 = Pump#1 Manual
3 = Pump 1 selected (units with two pumps)
4 = Pump#2 Manual
4 = Pump 2 selected (units with two pumps)
2
pump_del
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump automatic rotation delay
3
pump_per
no/yes
no
-
Pump Sticking Protection
Pump sticking protection
4
pump_sby
no/yes
no
-
Stop Pump During Standby
Pump stopped when the unit is in standby
5
pump_loc
no/yes
yes
-
Flow Checked if Pump Off
Water flow is checked when the pump is off
*Depends on the selected language (English by default).
Heat/Cool Config Menu – HCCONFIG
Point name
Status
Default
Unit
Displayed text*
Description
1
auto_sel
no/yes
no
-
Auto Changeover Select
Heating/Cooling automatic changeover
2
cr_sel
0 to 3
0
-
Cooling Reset Select
Cooling reset
3
hr_sel
0 to 3
0
-
Heating Reset Select
Heating reset
1=OAT, 0=None
2=Delta T
3= Analog (4-20mA)
0 = No reset
1 = Reset based on OAT
2 = Reset based on delta T
3 = Reset based on analog input (4-20 mA)
4
heat_th
-20.0 to 0.0
-4.0 to 32.0
-15.0
5.0
°C
°F
Heating OAT Threshold
Heating OAT threshold
5
boil_th
-15.0 to 15.0
5.0 to 59.0
-9.9
14.2
°C
°F
Boiler OAT Threshold
Boiler OAT threshold
6
ehs_th
-5.0 to 21.1
23.0 to 70.0
5.0
41.0
°C
°F
Elec Stage OAT Threshold
Electric heating stage OAT threshold
7
both_sel
no/yes
no
-
HSM Both Command Select
HSM command
8
ehs_back
no/yes
no
-
1 Elec Stage For Backup
Electric heating stage for back-up
9
ehs_pull
0 to 60
0
min
Electrical Pulldown Time
Electrical pull-down time: It defines the time
between starting the unit and determining whether
the electric heating stage should be started
10
ehs_defr
no/yes
no
-
Quick EHS For Defrost
Quick electric heating used for defrost
*Depends on the selected language (English by default).
Reset Config Menu – RESETCFG
Point name Status
Default
Unit
Displayed text*
Description
1
COOLING RESET
Cooling reset parameters
2
oatcr_no
-10.0 to 51.7
14.0 to 125.0
-10.0
14.0
°C
°F
OAT No Reset Value
OAT no reset value
3
oatcr_fu
-10.0 to 51.7
14.0 to 125.0
-10.0
14.0
°C
°F
OAT Full Reset Value
OAT full reset value
4
dt_cr_no
0 to 13.9
0 to 25.0
0
0
^C
^F
Delta T No Reset Value
Delta T no reset value
5
dt_cr_fu
0 to 13.9
0 to 25.0
0
0
^C
^F
Delta T Full Reset Value
Delta T full reset value