"humiFog direct" +0300073EN rel. 1.0 - 31.03.2017
The unit is ready to start when the following conditions are all satisfied:
•
the request from the external signal is greater than 10% or the humidity
/ temperature measured is less than the set point selected in steps 8/9
and 9/9 of the guided procedure;
•
the unit is in ON from the keypad and the zones are in RUNNING mode;
•
there an external signal that enables operation, i.e. the voltage-free
contact between M2.7-M2.8 on the c.pHC controller is closed;
•
the unit is ON from scheduler (if enabled);
•
the unit is ON from the supervisor (if on/off from the supervisor via
BMS or Ethernet port is enabled).
5.8.2
Set
Fig. 5.e
The information on the Set screen depends on the selected control mode.
When control by probe has been selected, this screen is used to set the
zone humidity / temperature set point and the limit probe set point, if
used. Each set point is associated with the amplitude of the proportional
band inside which the unit modulates atomisation.
Example: set point = 50%rH and band = 5%rH means that atomisation in
the room will be modulated starting from 45%rH.
Page
Title
Message
Value
Default
QB01
(QB02)
Set zone 1
(Set zone 2)
Main probe set point
0-100%rh/
0-40°C
50%rh / 25°C
Main probe band
0-10%rh/
0-10°C
5%rh / 2°C
Limit probe set point
0-100%rh/
0-40°C
80%rh / 15°C
Limit probe band
0-10%rh/
0-10°C
5%rh / 2°C
Tab. 5.g
5.8.3
Info menu
This is a read-only menu set out into different screens that display the
main data on the humiFog Direct unit.
Page
Message
Value/notes
QC01
Unit ON
Yes/No
Status
as per Ref. 4
on main screen
Request
0-100%
Production
0-80 kg/h
QC02
Maintenance hour counter
resettable
Unit hour counter
not resettable
QC03
Current date and time
dd/mm/yy ; h:min:s
Date and time of last shutdown
dd/mm/yy ; h:min:s
Time since last shutdown
days ; hours ; min
QC04*
Expansion online
Yes/No
Expansion firmware version
QC05
Model
Power supply
115/230 V
Phases
1
Power supply frequency
50/60 Hz
Pump rated production
40/80 kg/h
No. of zones
1 or 2
QC06
SW version
OS version
Boot version
Tab. 5.h
*Screen QC04 is only displayed if the second zone is used..
5.9 Graphic area 6 – Zone status icon
The symbol displayed in this graphic area identifies the status of the zone.
Important: in general, the zone status is different from the unit status.
Icon
Meaning
The zone is in standby or off
The zone is atomising
The zone has stopped due to an alarm
The zone is temporarily disabled
Tab. 5.i
5.10 Alarms
If there are active alarms, these are shown on the corresponding screen,
accessible by pressing the dedicated button (triangle with exclamation
mark).
The ALARM button starts flashing when an alarm occurs: pressing the
button once displays the type of alarm.
The alarms are divided into three categories:
•
potentially dangerous alarms that automatically stop production,
forcing the unit off until they are reset (alarm code AB***);
•
signals that do not stop production (alarm code AL***);
•
warnings only logged in the notification centre, neither signals nor
alarms that stop production (alarm code WR***).
For some alarm events, together with the signal the alarm relay is
activated. When the cause of the alarm is no longer present:
•
the humidifier and the alarm relay are reset, either automatically or
manually (see Chap. 7.1 “Alarm List”);
•
the message displayed can only be cleared manually
Even if no longer active, the alarm status will continues to be shown until
the “reset display” button is pressed. Alarms that are still active cannot be
reset. If more than one alarm is active, the display indicates all of these in
sequence. From the alarm screens the log can be displayed by pressing
ENTER. For the complete table of alarms see chap. 10 "Alarm table".