23
ENG
"humiFog direct" +0300073EN rel. 1.0 - 31.03.2017
Menu
Index
Description
D. Settings
(password_ _ _ _)
d. Network
Dd06
Disable network settings for the current unit (if Y, the network symbol disappears from the top right on
the main screen)
Dd07
Current unit request and production
Dd08
Check status and [%] production of unit 1/2/3/4 in the network
e. Manual mode
De01
Enable manual zone request, set request [%] and enable management of individual outputs on the
c.pHC to check function of electromechanical components
De02
Manual management of contactor, fill valve (FV), cabinet drain valve, bypass valve
De03
Manual management of fill valve in zone 1, drain valve in zone 1, fans in zone 1, set production [%] for
zone 1
De04
Manual management of fill valve in zone 2, drain valve in zone 2, fans in zone 2, set production [%] for
zone 2
De05
Manual management of unit status contact, alarm relay, fan on cabinet, WTS contact
f. Initialisation
Df01
Access configuration wizard and enable/disable wizard at power-on
Df02
Set screen language
Df03
Change password to access menu “D. Settings”
Df04
Set units of measure, international/Imperial
Df05
Set unit model
Df06
Restore default parameters
Df07
Enable USB port reading to update unit software
g. Supervision
Dg01
Serial address setting, enable unit on/off and control from the supervisor
Dg02
Select supervisor protocol
Dg03
BMS supervision port configuration: baud rate, stop bits, parity
Dg04
Ethernet supervision port configuration: DHCP, IP address, mask, gateway, DNS. Important: these values
must be supplied by the local network administrator
Dg05
BACnet configuration: address, maximum no. of masters, maximum no. of frames
h. Logout
Exit menu “D. Settings”: password must be entered on next access
Tab. 6.a
6.2 Scheduler
The Scheduler menu enables operation based on time bands.
Index
Description
Parameter
B01
Scheduler
Enable time bands
Default: time bands disabled
To configure the humidifier operating time bands for a specific day (24h),
use screen B02 (visible only if the scheduler is enabled). A time band can
be set with production disabled (OFF) or enabled (ON). Setting the ON
time band, the unit uses the main set point configured on screen Qb01.
Index
Description
Parameter
B02
Scheduler
Define daily and weekly time bands
Fig. 6.a
In the example shown here in Fig.7.a, the time band from 8.00 to 9.00 is
enabled for production. After 9.00, the humidifier will not be enabled.
unit of measure indication:
symbol displayed
Unit of measure
%
%rH
°C
Degrees Celsius
°F
Degrees Fahrenheit
Once the time bands have been defined for one day, press
to copy
the currently displayed bands (daily) to the next day. When the time
bands have been set, the display shows the
symbol.
6.3 Proportional control to an external
signal (modulating operation)
Atomisation is proportional to the value of an external signal Y, (selectable
from the following options: 0 to 1 Vdc; 0 to 10 Vdc; 2 to 10 Vdc; 0 to 20 mA; 4
to 20 mA). The maximum production Pmax corresponds to the maximum
value of the external signal Y, and will be the humidifier’s rated production.
The activation hysteresis hy is not settable by the user.
P
max
Steam_Pr
P
min
OFF
ON
0%
hy
2xhy
100%
Y
Y=
0…1Vdc
0…10Vdc
2…10Vdc
0…20mA
4…20mA
Fig. 6.b
Key:
Water_pr
Pressurised water production Y
External signal
P0
Max production
hy
Activation hysteresis
Pm
Min production
6.4 Autonomous control with humidity
probes
When using a main humidity control probe and an optional limit
humidity probe, atomisation is related to the % rH reading made by the
relative humidity probe and increases as the value read deviates from the
set point St. Maximum production Pmax corresponds to the case where
the humidity value, read by the probe, is BP away (proportional band)
from the set point. The activation hysteresis hy is not settable by the user.
Summary of Contents for humiFog direct