41
ENG
"humiFog direct" +0300073EN rel. 1.0 - 31.03.2017
ELECTRICAL SPECIFICATIONS
UA050DU*00
UA090DU*00
Power supply
120 Vac 60 Hz single-phase
120 Vac 60 Hz single-phase
Cabinet power cable
AWG 14
AWG 12
Power (cabinet only, without blowers)
0.28 kW (single-zone)
0.47 kW (single-zone)
0.38 kW (two zones)
0.57 kW (two zones)
Current (cabinet only, without blowers)
5.0 A (single-zone)
8.0 A (single-zone)
5.8 A (two zones)
8.8 A (two zones)
Maximum power (cabinet with blowers)
0.74 kW (single-zone)
0.93 kW (single-zone)
0.84 kW (two zones)
1.03 kW (two zones)
Maximum current (cabinet with blowers)
10.3 A (single-zone)
13.3 A (single-zone)
11.0 A (two zones)
14.0 A (two zones)
FLA (Full Load Amperes)
0.25HP/180W 4.2 A
0.5HP/370W 7.1 A
SCCR (Short Circuit Current Rating)
5 kA
5 kA
Minimum cable size required for blower power supply
AWG 14
AWG 12
Tab. 12.i
WATER CIRCUIT SPECIFICATIONS
UA050DU*00
UA090DU*00
Required feedwater quality
demineralised
demineralised
Required feedwater conductivity
5-80 µS/cm
5-80 µS/cm
Required feedwater pressure
3-8 bars
3-8 bars
Water inlet connection
3/4” GAS F
3/4” GAS F
Water drain connection
1/2” GAS F
1/2” GAS F
Water outlet connection
1/4” GAS F
1/4” GAS F
Water outlet pressure
70 bars
70 bars
Maximum capacity
50 l/h
90 l/h
Tab. 12.j
FUNCTIONAL SPECIFICATIONS
UA050DU*00
UA090DU*00
Number of probes allowed (temperature and/or humidity)
1 (single-zone) + limit
1 (single-zone) + limit
2 (two-zone) + limit
2 (two-zone) + limit
External signal or type of probes
0-10 V, 4-20 mA, 0-1 V, 2-10 V, 0-20 mA, NTC probe 0-10 V, 4-20 mA, 0-1 V, 2-10 V, 0-20 mA, NTC probe
Multi-probe
available
available
Webserver
available
available
Serial communication (via Ethernet and/or via RS485)
Modbus, BACnet
Modbus, BACnet
Tab. 12.k
12.3.3 CE version blower datasheet
Single blower units (for wall-mounting)
DLA02DF*00
DLA04DF*00
Dimensions
640 x 200 x 180 mm
940 x 200 x 180 mm
Weight
4.5 kg
5.6 kg
Packaged dimensions
755 x 235 x 295 mm
1050 x 235 x 295 mm
Packaged weight
5.7 kg
7.4 kg
Delivery and storage temperature
-10/50°C 0-90%
-10/50°C 0-90%
Operating temperature
2/40°C 5-95%
2/40°C 5-95%
Ingress protection (IP)
IP10
IP10
Conformity
CE
CE
Water fitting
M16x1.5 Male
M16x1.5 Male
Water outlet
M16x1.5 Male
M16x1.5 Male
Number of nozzles
2
4
Flow-rate (depending on the type of nozzles)
3.0 l/h - 5.6 l/h - 8.0 l/h
6.0 l/h – 11.2 l/h – 16.0 l/h
Power supply
230 Vac 50 Hz
230 Vac 50 Hz
Fan total air flow-rate
300 m3/h
600 m3/h
Blower connection cable
AWG 14
AWG 14
Maximum number of blower units (connected to one cabinet)
12
6
Tab. 12.l
Double blower units (for mounting in centre of corridor) CE version
DLA04DB*00
DLA08DB*00
Dimensions
640 x 200 x 400 mm
940 x 200 x 400 mm
Weight
9.2 kg
15.5 kg
Packaged dimensions
755 x 470 x 295 mm
1050 x 470 x 295 mm
Packaged weight
11.4 kg
18.0 kg
Delivery and storage temperature
-10/50°C 0-90%
-10/50°C 0-90%
Operating temperature
2/40°C 5-95%
2/40°C 5-95%
Ingress protection (IP)
IP10
IP10
Conformity
CE
CE
Water fitting
M16x1.5 Female
M16x1.5 Female
Water outlet
M16x1.5 Female
M16x1.5 Female
Number of nozzles
4
8
Flow-rate (depending on the type of nozzles)
6.0 l/h – 11.2 l/h – 16.0 l/h
12.0 l/h – 22.4 l/h – 32 l/h
Power supply
230 Vac 50 Hz
230 Vac 50 Hz
Fan total air flow-rate
600 m3/h
1,200 m3/h
Blower connection cable
AWG 14
AWG 14
Maximum number of blower units (connected to one cabinet)
6
3
Tab. 12.m
Summary of Contents for humiFog direct