30
ENG
"humiFog direct" +0300073EN rel. 1.0 - 31.03.2017
8.4 List of BACnet parameters
Type
Section
BACNet
Parameter
Variable
Dir
Binary values
Unit status
0
Unit on/off
UnitOn
R
Alarms
1
Circuit breaker intervention
Al_CircBreaker.Active
R
2
High pressure switch intervention
Al_HiPSwitch.Active
R
3
High pressure
Al_HiP.Active
R
4
Low pressure
Al_LoP.Active
R
5
High pressure on bypass
Al_HiPByPassBlk.Active
R
6
High pressure on bypass
Al_HiPByPass.Active
R
7
High temperature on bypass
Al_HiTByPassBlk.Active
R
8
High temperature on bypass
Al_HiTByPass.Active
R
9
Low pressure on bypass
Al_LoPByPass.Active
R
10
Zone drain valves error
Al_Drain.Active
R
11
Expansion offline
Al_ExpOffline.Active
R
12
Warning high temperature on bypass
Wr_HiTByPass.Active
R
13
Retain memory error
Al_Retain.Active
R
14
Retain memory writes error
Al_RetainWrite.Active
R
15
Main probe 1 error
Al_MainPrb_1.Active
R
16
Limit probe 1 error
Al_LimPrb_1.Active
R
17
Main probe 2 error
Al_MainPrb_2.Active
R
18
Limit probe 2 error
Al_LimPrb_2.Active
R
19
Low pressure trasducer error
Al_PressByPass.Active
R
20
Bypass temperature probe error
Al_TempByPass.Active
R
21
High pressure transducer error
Al_Press.Active
R
22
Missing model
Al_MissModel.Active
R
23
Water treatment system alarm
Al_WTS.Active
R
24 - 31
Wireless probe offline 1 - 8
Al_WPrb_1 - 8.Active
R
32
Main probe 1 from wireless error
Al_WPrbMain_1.Active
R
33
Limit probe 1 from wireless error
Al_WPrbLim_1.Active
R
34
Main probe 2 from wireless error
Al_WPrbMain_2.Active
R
35
Limit probe 2 from wireless error
Al_WPrbLim_2.Active
R
36 - 39
Unit 1 - 4 alarm
Al_NetUnit_1 - 4.Active
R
40
Change oil
Al_Maint_50.Active
R
41
Maintenance
Wr_Maint_1000.Active
R
42
Maintenance required
Al_Maint_3000.Active
R
Remote control
43
Alarms reset
Alarms.AlrmResBySV
RW
44
Unit on/off from supervisor
OnOff_Status.SVOn
RW
P.I.V.
Unit status
0
Unit Status
UnitStatus
R
Analog values Unit status
0
Request zone 1
ReqMsk_1
R
1
Request zone 2
ReqMsk_2
R
2
Production zone 1
Prod_1
R
3
Production zone 2
Prod_2
R
4
Water consumption 1
WProd_1
R
5
Water consumption 2
WProd_2
R
Inputs
6
Main probe 1
MainPrb_1
R
7
Main probe 2
MainPrb_2
R
8
Limit probe 1
LimPrb_1
R
9
Limit probe 2
LimPrb_2
R
10
Pressure on bypass
PressByPass
R
11
Pressure on mail line
Press
R
12
Bypass temperature
TempByPass
R
13-15-17-19- 21-23-25-27
Humidity from wireless probe 1 - 8
Inputs_WPrbs.WirelessPrbVal_1 - 8.Hum
R
14-16-18-20-22-24-26-28
Temperature from wireless probe 1 - 8
Inputs_WPrbs.WirelessPrbVal_1 - 8.Temp
R
Remote control
29
Unit request from supervisor zone 1
Regulation.SVReq_1
RW
30
Unit request from supervisor zone 2
Regulation.SVReq_2
RW
31
Setpoint zone 1 (humidity)
RegCfg_1.SetP_hum
RW
32
Setpoint zone 1 (temperature)
RegCfg_1.SetP_temp
RW
33
Setpoint limit zone 1 (humidity)
RegCfg_1.SetPLim_hum
RW
34
Setpoint limit zone 1 (temperature)
RegCfg_1.SetPLim_temp
RW
35
Setpoint zone 2 (humidity)
RegCfg_2.SetP_hum
RW
36
Setpoint zone 2 (temperature)
RegCfg_2.SetP_temp
RW
37
Setpoint limit zone 2 (humidity)
RegCfg_2.SetPLim_hum
RW
38
Setpoint limit zone 2 (temperature)
RegCfg_2.SetPLim_temp
RW
Tab. 8.b
Summary of Contents for humiFog direct
Page 2: ......
Page 4: ...4 ENG humiFog direct 0300073EN rel 1 0 31 03 2017...
Page 6: ...6 ENG humiFog direct 0300073EN rel 1 0 31 03 2017...
Page 43: ......