Troubleshooting
Fault Code
and Message
Fault
Cause
Correction
Fault 71:
VCM drop
4 Firmware
update failure
A firmware
update failed on
VCM drop 4
Poor harness connection or
process failure
Do a software reset from the
System Menu to retry. Do a check
of the harness connections on
VCM Drop 4
Fault 72:
VCM drop
5 Firmware
update failure
A firmware
update failed on
VCM drop 5
Poor harness connection or
process failure
Do a software reset from the
System Menu to retry. Do a check
of the harness connections on
VCM Drop 5
Fault 73:
VCM drop
6 Firmware
update failure
A firmware
update failed on
VCM drop 6
Poor harness connection or
process failure
Do a software reset from the
System Menu to retry. Do a check
of the harness connections on
VCM Drop 6
Fault 74:
VCM drop
7 Firmware
update failure
A firmware
update failed on
VCM drop 7
Poor harness connection or
process failure
Do a software reset from the
System Menu to retry. Do a check
of the harness connections on
VCM Drop 7
Fault 75:
VCM drop
8 Firmware
update failure
A firmware
update failed on
VCM drop 8
Poor harness connection or
process failure
Do a software reset from the
System Menu to retry. Do a check
of the harness connections on
VCM Drop 8
Damaged harness
Do a check of the connections
to section 1 valve and section 9
valve. Also do a check of pin 3
(blue wire) on harnesses of VCM
drop 1.
Internal hub problem
Contact CapstanAG to repair or
replace the hub.
Fault 76:
Section 1 Valve
Short Circuit
Section 1 Valve
Short Circuit
Servo valve failure
Repair or replace the servo valve
Damaged harness
Do a check of the connections
to section 1 valve and section 9
valve. Also do a check of pin 3
(blue wire) on harnesses of VCM
drop 1.
Internal hub problem
Contact CapstanAG to repair or
replace the hub.
Fault 77:
Section 2 Valve
Short Circuit
Section 2 Valve
Short Circuit
Servo valve failure
Repair or replace the servo valve
©
2021 Capstan Ag Systems, Inc.
93
PinPoint
™
III ENVELOP
Summary of Contents for PinPoint III ENVELOP
Page 6: ......
Page 65: ...TM Operation 2021 Capstan Ag Systems Inc 65 PinPoint III ENVELOP...
Page 66: ...TM Operation Nozzle Spacing 50 cm 2021 Capstan Ag Systems Inc 66 PinPoint III ENVELOP...
Page 67: ...TM Operation 2021 Capstan Ag Systems Inc 67 PinPoint III ENVELOP...
Page 69: ...TM Operation 2021 Capstan Ag Systems Inc 69 PinPoint III ENVELOP...
Page 71: ...TM Operation 2021 Capstan Ag Systems Inc 71 PinPoint III ENVELOP...
Page 72: ...TM Operation Nozzle Spacing 20 in 2021 Capstan Ag Systems Inc 72 PinPoint III ENVELOP...
Page 73: ...TM Operation 2021 Capstan Ag Systems Inc 73 PinPoint III ENVELOP...
Page 75: ...TM Operation 2021 Capstan Ag Systems Inc 75 PinPoint III ENVELOP...
Page 76: ...TM Operation 2021 Capstan Ag Systems Inc 76 PinPoint III ENVELOP...
Page 84: ...TM Maintenance 2021 Capstan Ag Systems Inc 84 PinPoint III ENVELOP...
Page 116: ...TM Troubleshooting 2021 Capstan Ag Systems Inc 116 PinPoint III ENVELOP...
Page 122: ...TM Schematics System Layout Figure 42 2021 Capstan Ag Systems Inc 122 PinPoint III ENVELOP...
Page 124: ...TM Schematics 2021 Capstan Ag Systems Inc 124 PinPoint III ENVELOP...
Page 127: ......