![background image](http://html.mh-extra.com/html/candk-systems/system-2316e/system-2316e_installation-instructions-manual_478078003.webp)
3
SYSTEM 2316E/2316EC Installation Manual
Keypad Requirements
The keypad may not have the EMERGENCY symbol (
) on it.
The System 2316EC has not been evaluated by Underwriters Labora-
tories, Inc.
The System 2316E is in compliance with Underwriters Laboratories, Inc.
Standards UL 985, Household Warning System Units; UL 1023, House-
hold Burglar Alarm System Units; and UL 1635, Digital Burglar Alarm
Communicator System Units.
The following programming restrictions
must be observed to meet UL standards
.
UL COMPLIANCE
1. The audible must be programmed to sound at least four minutes
before silencing.
2. No zone may be programmed for silent alarm.
3. Fire zones must be programmed for 3-pulse temporal audible
alarm. A 3-pulse temporal is not to be used on non-fire zone
types.
4. Burglar zones must be programmed for a steady audible.
5. Burglar loops (non-24-hour loops) must be programmed for NO/
NC with EOL.
6. No Entry Delay may be greater than 45 seconds.
7. No Exit Delay may be greater than 60 seconds.
8. The Dynamic Battery Test must be enabled.
9. The Unit Status Report must be enabled.
10. The 24-hour Check-in must be enabled.
11. No Delay Before Dial may be programmed for the communicator.
12. The unit must not be programmed to dial a police station.
13. Use screws (supplied) to secure cover, or a lock must be installed
on the cabinet.
14.All devices must be UL listed.
15. For residential fire applications, use the C&K Model 2350-SUP for
Circuit Supervision.
16. Telco connections must be made using 0.4 mm (26 AWG) or larger
wire.
The following additional restrictions must be observed to meet Grades
A and B Mercantile Premises Alarm Systems/Safe and Vault Alarms
Systems under UL 365, Police Station Connected Burglar Alarm Units
and Systems and UL 609, Local Burglar Alarm Units and Systems.
1. The audible must be programmed to sound at least 15 minutes
before silencing.
2. The ring-back function must be activated.
3. The arming mode must be programmed "goof-proof".
4. The control panel must be mounted in an enclosure that is:
(a) Attack-resistant (C&K Model # 2330-UAC)
(b) Secured with a key-lock and #6 X 1¼" sheet metal
screws.
(c) Tamper protected against cabinet door opening and
removal from mounting surface.
(d) For safe and vault applications the control panel must be
monitored by a UL Listed shock sensor suitable for the
protection of sheet metal enclosures.
5. The Ademco Model AD10-12 bell with Model AB bell housing
must be used.
6. The power and tamper wiring between the bell and control panel
must be completely enclosed in rigid conduit or electric metallic
tubing for a Grade A system or flexible conduit for a Grade B
system.
7. Zone(s) monitoring tamper circuitry must be 24 hours and non-
shuntable.
INSTALLATION
Mounting
The System 2316E/2316EC should be mounted in a location that allows
convenient access to AC power, telephone connections, and earth ground.
1. Remove the circuit board from the cabinet. This will prevent pos-
sible damage to the circuit board when removing the knockouts.
2.Remove the knockouts, as required.
3.Mark the screw mounting holes on the wall.
4.Mount the cabinet at the desired height and pass the cables through
the knockouts.
5. Replace the circuit board, remembering to connect the ground lug
to the lower left corner of the circuit board.
6. Reconnect the spade lug to the lower door hinge. This provides the
earth ground connection for the door.
EUROPEAN COMPLIANCE
System 2316EC
This alarm control panel and its accessories have been tested to and
conforms with the following Council Directives:
Council Directive 89/336/EEC, for Residential, Commercial, and Light
Industrial Applications according to standards EN 50081-1 and
EN#50082-1.
Council Directive 73/23/EEC, as detailed in Standards EN-60950
Amendments 1-4.
See section regarding AC Power (2316EC) for basic installation notes.
Earth Ground
To ensure the effectiveness of the lightning and transient protection
circuits, the control panel
must
be connected to "Earth Ground". Ideally,
this should be a common ground to the power lines, telephone system,
and security system. This type of ground, called a "Unified Earth Ground",
provides the best protection. The ground connection, from a grounding
rod, cold water pipe or other established ground point, is made to the
green/yellow jacketed wire, providing a ground to the panel housing.
Power
Lines
Control
Panel
Unified Earth Ground
with Bonded Ground Roots
Telephone
Earth Ground
Power Line
Earth Ground
Telephone
Lines
Figure 1
Connecting to Earth Ground
Scope of This Manual
This manual contains basic installation and programming information for the
System 2316E and 2316EC. Additional information about remote program-
ming, may be found in the Commander II/Monitor II Operating Manual.
INTRODUCTION
Accuracy
This manual has been carefully checked for accuracy. However, C&K
SYSTEMS assumes no liability for inaccuracies or actions resulting from
the use of this manual. In addition, C&K reserves the right to modify the
System 2316E/2316EC hardware, software, and manuals without prior
notice.
Steady Audible
NO/NC with EOL
.
..
BURGLAR LOOP
No Delay Before Dial
Not shuntable
.
Supervised
-latching for heat
-resetting for smoke
.
3-pulse temporal audible
.
24-hour arming
.
No Delay Before Dial
.
FIRE LOOP
Zone Programming