SYSTEM 2316E/2316EC Installation Manual
Command Location 2E: Audible/Visual Switches
Default Values
(1)
(2)
(3)
(4)
(5)
1
0
0
0
1
2
E
Digit Position (1): Entry Pre-alarm Enable
0 = No
1 = Yes: sounds keypad buzzers during entry delay
Digit Position (2): Exit Pre-alarm Enable
0 = No
1 = Yes: sounds keypad buzzers during exit delay
Digit Position (3): Bell Reverse Operation
0 = No
1 = Yes: supplies bell voltage in non-alarm state; Bell requires external power supply
Digit Position (4): Ring Back Enable
0 = No
1 = Yes: Automatic Bell test after arming (and Exit Delay has expired) for local or non-supervised
accounts; follows closing report for supervised accounts; sounds bells for 2 seconds.
Digit Position (5): Disable Loop LEDs
0 = No
1 = Yes: turns off keypad zone LEDs after 5 minutes
Command Location 2F: Unit Control
Default Values
(1)
(2)
(3)
(4)
(5)
0
0
1
1
1
2
F
Digit Position (1): Local System Only
0 = No
1 = Yes: disables all communications except RPS
Digit Position (2): Daily Dynamic Battery Test Enable
0 = No
1 = Yes: performs a 2-minute battery test (under load conditions) once every 4 hours
Digit Position (3): Four Minute Power-Up Delay Enable
0 = No
1 = Yes: all alarms suppressed for 4 minutes on power-up
Digit Position (4): Soft Zone Operation Enable
0 = No
1 = Yes: allow use of Emergency (E), Fire (F), and Police (P) keys (See also CL 27 - 29)
Digit Position (5): AC Power Line Frequency
0 = 50 Hz
1 = 60 Hz
A
B
C
D
E
F
Hexadecimal Value
Key Strokes
0
1
2
3
4
5
PROGRAMMING CONVERSIONS
CL 2E and 2F