17
SYSTEM 2316E/2316EC Installation Manual
Command Locations 17 - 1E & 40 - 47: Loop Reporting Codes
(1)
(2)
(3)
(4)
(5)
(6)
0
1
E
1
0
0
17 = Loop 1
18 = Loop 2
19 = Loop 3
1A = Loop 4
1B = Loop 5
1C = Loop 6
1D = Loop 7
1E = Loop 8
40 = Loop 9
41 = Loop 10
42 = Loop 11
43 = Loop 12
44 = Loop 13
45 = Loop 14
46 = Loop 15
47 = Loop 16
7
1
**Default Values
Loop 1 shown
#
**Default Values are different
for each loop. Refer to the
SYSTEM 2316E/2316EC
Programming Worksheet at
the end of this manual.
Digit Positions (1) & (2): Alarm Reporting Code
Program 00 to disable Event Reporting for a loop.
Digit Positions (3) & (4): Restore Reporting Code
Program 00 to disable Event Reporting for a loop.
Digit Positions (5) & (6): Shunt Reporting Code
P
rogram 00 to disable Event Reporting for a loop.
Command Locations 1F - 26, & 49 - 50: Loop Control
(1)
(2)
(3)
(4)
(5)
(6)
1
2
1
3
3
3
F
1
1F = Loop 1
20 = Loop 2
21 = Loop 3
22 = Loop 4
23 = Loop 5
4B = Loop 11
4C = Loop 12
4D = Loop 13
4E = Loop 14
4F = Loop 15
50 = Loop 16
24 = Loop 6
25 = Loop 7
26 = Loop 8
49 = Loop 9
4A = Loop 10
**Default Values
Loop 1 shown
#
**Default Values are different
for each loop. Refer to the
SYSTEM 2316E/2316EC
Programming Worksheet at
the end of this manual.
Digit Position (2): Loop Response Time
Digit Position (1): Alarm Receiver Select
0 = Receiver 1 with Receiver 2 as backup
1 = Receiver 1 only
2 = Receiver 2 only
3 = Receiver 1 and Receiver 2 (Dual Reporting)
0 = 5 milliseconds
1 = 250 milliseconds
2 = 500 milliseconds
3 = 750 milliseconds
Digit Position (3): Loop Restore Type
0 = No Restoral Report sent
1 = Restoral sent when loop normal
2 = Restoral sent when loop normal and bell silences
3 = Restoral sent when loop normal and system
disarmed
Digit Position (4): Loop Arming Type
1 = Interior: delayed during E/E delays
2 = Instant
3 = Delay
4 = Long Delay: delay two times as long
5 = Day/Instant: buzzer on day fault
6 = Day/Delay: buzzer on day fault
7 = Day/Instant with bell
8 = Day/Delay with bell
9 = 24 Hours: always armed
Digit Position (5): Loop Bell Type
1 = 3-pulse temporal
2 = Pulsing
3 = Steady
4 = Chirp
5 = Silent with no LED
6 = Silent with LED
Digit Position (6): Loop Circuit Type
1 = Normally Open Circuit
2 = Normally Closed Circuit
3 = End Of Line (EOL)
4 = Supervised, bell latched
5 = Supervised, bell not latched
NOTE:
A Loop programmed as type 4 or 5 will report
any open as a Trouble condition, regardless of
panel armed status.
A
B
C
D
E
F
Hexadecimal Value
Key Strokes
0
1
2
3
4
5
PROGRAMMING CONVERSIONS
CL 17 - 1E & 40 - 47, 1F - 26 & 49 - 50