Appendix C. PS24 24 Ah Power Supply and 10 x 12 inch Enclosure
C-11
16.
Plug the connector on the BP24 24 Ah battery wiring harness into the only
battery connector on the CH150 or PS150 (located adjacent to the charge
ports) or into the
Battery – Internal
connector on the PS100 or the
INT
connector on the CH100.
Since the power coming into the enclosure is regulated power
coming from the external enclosure, the wiring inside the ET107
station enclosure needs to be different than the standard wiring.
17.
If this is a retrofit, inside of the ET station enclosure, wires come through
the enclosure wall from the
POWER
connector on the back of the station
that used to be wired into the charge ports of the PS100 or PS150. You have
three options:
a.
If you received a new
POWER
connector with your kit, remove the old
POWER
connector by removing the plastic nut on the back of the
station that holds the
POWER
connector in place. Remove the old
connector and replace it with the new one, placing the foam washer
inside the enclosure. Tighten the plastic nut. Plug the plastic plug of the
new
POWER
connector into the 12V port.
b.
If you’re working with the old
POWER
connector, connect the black
wire of the
POWER
connector to the ground connector on the gray
terminal strip, and the red wire to the
12V
connector on the terminal
strip. The wire and plug previously used with the PS100 or PS150 can
be discarded
c.
If you’re experienced with electrical work, butt splice the wires of the
POWER
connector to the wires on the plastic plug (red to red and
black to black). Plug the plastic plug into the
12V
terminal.
18.
An extra loop of ground wire was sent with the station. Use it to ground the
enclosure to the grounding rod system. The external ground lug is mounted
on the bottom left hand corner of the 10-inch-by-12-inch enclosure.
19.
Move the switch to the
ON
position, and test the station.
20.
After everything checks out, find the gray duct putty that was included in the
enclosure supply kit. Seal the cable-entry conduit by placing putty on the
inside and outside of it. Push the putty down into the cable entries.
The enclosure needs to be sealed up tight, so don’t be stingy
with the putty.
21.
Put both bags of desiccant inside of the enclosure.
22.
Stick the humidity indicator card on a wall inside of the enclosure.
Pink on the humidity indicator card means it’s time to change
the desiccant. Change the desiccant at least every year.
However, it’s often wise to change the desiccant every six
months.
23.
Close the lids on the external enclosure and the ET107 enclosure.
NOTE
CAUTION
CAUTION